MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Device address supervision: The system checks that all configured devices on the addressable
device circuit and the Serial Interface Circuit respond to an address poll. The system reports a
trouble condition if the following conditions are detected:
Configured device is missing.
Unconfigured device is installed.
Two devices are programmed with the same address location.
Loop card is shorted.
When "loop card is shorted," trouble is detected by the panel; all devices on the loop card are
disabled and will not be able to annunciate any events.

REGULATORY STANDARDS

The MPC-6000 / MPC-7000 control units and the RND-2 network annunciator meet the
requirements of industry and government regulatory agencies as noted.

Federal Communications Commission

The MPC-DACT meets the Class A requirements of the Code of Federal Regulations (CFR
47), Part 15, for electromagnetic field emissions. The MPC-DACT also meets the requirements
of the Code of Federal Regulations (CFR 47), Part 68, for connection of equipment to the
public switched telephone network.

Underwriters Laboratories

The MPC-6000 / MPC-7000 Fire Alarm control units and the RND-2 network annunciator are
listed under UL Standard 864 for compliance to NFPA Standard 72 for fire service.