MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL

MPC-REL (Optional Releasing Module for MPC-6000 only)

 Two power limited releasing circuits
 Four non-power limited open collector circuits
 Releasing Circuits are rated at 1.5A at 24VDC, filtered
 Open Collector Circuits are rated at 200mA at 24VDC, filtered
 Maximum cumulative current output must not exceed 3A
 Each Releasing Circuit requires REL-EOL module (P/N 500-696359) installed as close as
possible to the last solenoid for proper wire supervision
 Requires an RPT-1 transformer
REL-EOL module (P/N 500-696359) is required for supervision of open and short circuits on
the releasing circuit. REL-EOL must be in the same enclosure or close nippled to the last
solenoid in the loop.