Attention Installer; Electrical Connections - GE JCKS10 Installation Instructions Manual

27”/30" built-in wall oven
Hide thumbs Also See for JCKS10:
Table of Contents

Advertisement

Installation Instructions

Electrical Connections

B

ATTENTION INSTALLER

All electric wall ovens must be hard wired
(direct wired) into an approved junction
box. A plug and receptacle is NOT permitted
on these products.
DO NOT shorten the flexible conduit.
The conduit strain relief clamp must be
securely attached to the junction box
and the flexible conduit must be securely
attached to the clamp. If the flexible
conduit will not fit within the clamp, do not
install the oven until a clamp of the proper
size is obtained.
NOTE TO ELECTRICIAN: The 3 power
leads supplied with this appliance are
CSA recognized for connection to heavier
gauge household wiring. The insulation
of these 3 leads is rated at temperatures
much higher than the temperature rating
of household wiring. The current carrying
capacity of the conductor is governed
by the wire gauge and the temperature
rating of the insulation around the wire.
WARNING:
connection of aluminum house
wiring to copper leads can
result in an electrical hazard or fire.
Use only connectors designed for
joining copper to aluminum and follow
the manufacturer's recommended
procedure closely.
Improper
Turn off the circuit breaker or remove fuses
B1
to the oven branch circuit.
With the oven supported on a table or
B2
platform in front of the cabinet opening,
connect the flexible conduit to the electrical
junction box as shown below. Position the
conduit in such a manner that it will lie on
top of the oven in a natural loop when the
oven is installed. You will need to purchase
an appropriate strain relief clamp to
complete the connection of the conduit
to the junction box.
Conduit
Place oven on a
support to assist in
connecting conduit
This oven is supplied with a 123 cm (48")
B3
long flexible conduit consisting of:
3 insulated conductors (copper)
1 bare ground conductor (copper)
Attach conductors to residence wiring as
B4
shown by wiring diagram.
CONDUIT
FROM
OVEN
RED
14 AWG
BLACK
14 AWG
BARE
COPPER
14 AWG
BLACK
GROUND
CSA APPROVED
JUNCTION BOX AND COVER
9
Junction Box
Location
BARE
GROUND
RED
WHITE
BLACK
Strain Relief Clamp
(not included)
must be used at
Junction Box
WHITE
CSA APPROVED
(NEUTRAL)
14 AWG
CONNECTOR
TO BREAKER PANEL
WHITE
RED
#12-#10 AWG-COPPER
NMD90 WIRE. FUSE 20
AMP CIRCUIT BREAKERS
GROUND
WIRE