Boiler Ignition; Boiler Operation Is Now Automatic; Ignition Block; Temperature Overload Block - Immergas EOLO Mini S Instruction Booklet

Table of Contents

Advertisement

Boiler ignition. Before switching on the boiler, check that
ES
the system is fi lled with water and that gauge (1) indicates
a pressure of 1÷1,2 bar.
- Open the gas valve downstream of the boiler.
PL
- Turn the main switch (4) to the setting Heating ( ) to
enable standby mode, i.e. boil er on but no fl ame present
(both indicator lamps switched off ), this status remains
CZ
until the burner is ignited and the cir cu la tion pump is
activated (indicator lamp 2 ON).
With the switch set to ( ) the heating regulation se lec tor
HR
(5) is used to regulate the temperature of ra di a tors, rotate
clockwise to increase the temperature and counterclockwise
to decrease.
SL

Boiler operation is now automatic.

Ignition block - Red indicator lamp (3) ON. Each time
heating is required the boiler is activated automatically. If
HU
this does not oc cur within 10 seconds, the boiler activates
an "ig ni tion block" (indicator lamp 3 ON). To eliminate the
block, rotate the main switch (4) temporarily to the Reset
IE
position. On initial ignition or following a pro longed period
of disuse the ignition block may need to be inhibited. If this
function is activated re peat ed ly, con tact a qualifi ed technician
for assistance (e.g. Immergas Technical Services Centre).
Temperature overload block – Red indicator lamp (3)
fl ashing. During normal operation, if a fault causes a in-
ternal tem per a ture overload condition, boiler operation is
shut off .
To startup the boiler, set the main switch (4) tem po rar i ly
to Reset. If this fault occurs repeatedly, contact a qualifi ed
technician for assistance (e.g. Immergas Technical Services
Centre).
Air pressure switch activation failure - Red in di ca tor
lamp (3) and yellow indicator lamp (2) fl ash ing.  is fault
condition occurs if the intake or ex haust pipes are blocked
or a fan fault. In this case contact a qualifi ed technician
for assistance (e.g. Immergas Technical Services Centre). If
normal con di tions are restored the boiler resumes operation
with out requiring reset.
Insuffi cient circulation water – Red indicator lamp (3)
ON, yellow indicator lamp (2) fl ash ing.  is occurs when
the boiler is overheating because of insuffi cient circulation of
water in the primary circuit; causes may be the following:
- low circulation system; check that no shutoff devices are
closed on the heating circuit or that any air bub bles are
present in the system;
- circulator blocked; release (see page 113).
- the water pressure in the heating circuit is not enough to
guarantee the correct functioning of the boiler. Check that
pres sure is between 1 and 1,2 bar;
If normal con di tions are restored the boiler resumes operation
with out requiring reset.
If this function is activated re peat ed ly, con tact a qualifi ed
technician for assistance (e.g. Immergas Technical Services
Centre).
116
Sensor fault - Yellow indicator lamp (2) fl ashing. On igni-
tion, if the control unit detects a fault on the NTC sensor, the
boiler does not start; in this case contact a qualifi ed technician
for assistance (e.g. Immergas Technical Services Centre).
Boiler shutdown. Turn off the main switch (4) by setting
to "0" (yellow indicator lamp 2 OFF) and close the gas sup-
ply valve upstream of the appliance. Nev er leave the boiler
switched on if left unused for pro longed periods.
Heating system pressure.
Periodically check the system water pressure.  e boiler pres-
sure gauge should read a pressure be tween 1 and 1,2 bar.
If the pressure falls below 1 bar (with the circuit cool) restore
normal pressure via the valve located at the bottom of the boiler
(see fi gure).
N.W.: close the valve on completion.
If pressure values reach around 3 bar the safety valve may
be activated.
In this case contact a professional technician for as sist ance.
In the event of frequent pressure drops, contact qual i fi ed
personnel for assistance to eliminate system leak age.
Bottom view
Gas cock
Domestic water inlet cock
Draining the system.
To drain the system completely, use the drain valve (see fi gure
above and on page 114).
Before draining, ensure that the fi lling valve is closed.

Anti-freeze protection.

 e boiler is equipped as standard with an anti-freeze fun-
ction ( ) that activates the pump and burner when sys tem
water temperature falls below 8°C and de ac ti vates once
temperatures reach 43°C.  e anti-freeze function is gua-
ranteed if the boiler is totally operative and not in "block"
status, when connected to the elec tri cal power supply and
the main switch is set ( ) mode. To avoid continued ope-
ration in the event of prolonged absence, the sys tem must
be drained completely or anti-freeze sub stanc es should be
added to the heating system wa ter. In appliances subject to
fre quent draining, the system must be refi lled with suit a bly
treated water to elim i nate hardness that may cause limescale
formation.
Drain cock
Filler cock

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents