External Grille - Immergas EOLO Mini S Instruction Booklet

Table of Contents

Advertisement

• Extensions for horizontal kit.  e horizontal in take/
ES
exhaust kit Ø 80/125 can be extended up to a maximum
horizontal length of 7300 mm including the terminal grille
and excluding the concentric bend on output of the boiler
PL
and the adapter Ø 60/100 in Ø 80/125 (see fi gure).  is
confi guration cor re sponds to a resistance factor of 100. In
these cas es spe cifi c extensions must be requested.
CZ
HR
SL
N.W.: when installing the ducts, a section clamp with pin
HU
must be installed every 3 metres.
• External grille. N.W.: for safety purposes, do not totally or
partially obstruct the boiler intake/exhaust terminal even
IE
temporarily.
Vertical kit with aluminium tile Ø 80/125. Kit as sem bly:
install the concentric fl ange (2) on the cen tral hole of the
boiler taking care to insert the seal (1) supplied with the kit
and tighten by means of the screws supplied with the boiler.
Fit the male section (smooth) of the adapter (3) coin the
female section of the concentric fl ange (2). Installing the
imitation alu min i um tile. Replace the tile with the alumi-
nium sheet (5), shaping it to ensure off -fl ow of rainwater.
Position the fi xed half-shell (7) on the aluminium tile and
insert the intake/exhaust pipe (6). Fit the con cen tric ter mi nal
Ø 80/125 with the male section (6) (smooth), in the female
section of the adapter (3) (with lip seal) to the end stop,
ensuring that washer (4) si already fi t ted to ensure sealing
effi ciency of all cou plings.
108
• Snap fi t extension pipe fi ttings and concentric elbows Ø
80/125. To install snap-fi t ex ten sions with other elements
of the boiler assembly, pro ceed as follows: fi t the concentric
pipe or elbow with the male section (smooth) on the female
sec tion (with lip seal) to the end stop on the previously
installed to ensure sealing effi ciency of the cou plings.
Caution: if the exhaust terminal and/or extension concen-
tric pipe needs shortening, consider that the internal duct
must always protrude by 5 mm with re spect to the external
duct.
 is specifi c terminal enables fl ue exhaust and air intake in
a vertical direction.
N.W.: the vertical kit Ø 80/125 with aluminium tile en a bles
installation on terraces and roofs with max i mum gradient
of 45% (24°) and the height between the ter mi nal cap and
half-shell (374 mm) must be strictly observed.
 is vertical kit confi guration can be extended to a maximum
length of 12200 mm in a vertical straight route, including
the terminal (see fi gure next page).  is con fi g u ra tion cor-
responds to a resistance factor of 100. In this case specifi c
extensions must be re quest ed.
Terminal Ø 60/100 can also be used for vertical ex haust,
in conjunction with concentric fl ange code no. 3.011141
(sold separately). height between the ter mi nal cap and half-
shell (374 mm) must be strictly ob served (see drawing next
page).
 is vertical kit confi guration can be extended to a maximum
length of 4700 mm in a vertical straight line, including the
terminal (see fi gure next page).
 e kit comprises:
1 - Seal (1)
1 - Female concentric fl ange (2)
1 - Adapter Ø 60/100 for Ø
80/125 (3)
1 - Washer(4)
1 - Aluminium tile (5)
1 - Int./exh. concentric pipe Ø
80/125 (6)
1 - Fixed half-shell (7)
1 - Mobile half-shell (8)