Superior SDDV-35 Installation Instructions Manual page 20

Direct vent sddv-35/40 series
Table of Contents

Advertisement

I. Continue installation of horizontal/inclined
sections - Continue with the installation of the
straight vent sections in horizontal/inclined run
as described in Step E. Install support straps
every 5 ft. (1.52 m) along horizontal/inclined
vent runs using conventional plumber's tape.
See Figure 31. It is very important that the
horizontal/inclined run be maintained in a
straight (no dips) and recommended to be in
a slightly elevated plane, in a direction away
from the fi replace of 1/4" rise per foot (20 mm
per meter) which is ideal, though rise per foot
run ratios that are smaller are acceptable all the
way down to at or near level.
It is important to maintain the required clear-
ances to combustibles: 1" (25 mm) at all sides
for all vertical runs; and 3" (76 mm) at the top,
1" (25 mm) at sides, and 1" (25 mm) at the
bottom for all horizontal/inclined runs.
J. Assemble vent run to exterior wall - If not
previously measured, locate the center of the
vent at the exterior wall. Prepare an opening as
described in Step B. Assemble the vent system
to point where the terminus of the last section is
located relative to the exterior surface to which
the termination is to be attached (see Figures
32 & 33 and Table 12 on Page 21.
If the terminus of the last section is not within
this distance, use the telescopic vent section
SV4.5LA, as the last vent section. For wall
thicknesses greater than that shown in Figure
33 and Table 12 on Page 21. This table lists
the additional venting components needed (in
addition to the termination and adapter) for a
particular range of wall thicknesses.
K. Attach termination adapter - Attach the
adapter (adapter - SV4.5RCH - provided with the
termination) to the vent section or telescoping
vent section, elbow or appliance collar as shown
in Figures 32 & 33 in the same manner as any
SV4.5 vent component (refer to Step E).
L. Install Firestop/Spacer at exterior wall
- When using the square termination, install
SV4.5HF (Secure Vent), SF4.5HF (Secure Flex)
Firestop/Spacer over the opening at the exterior
side of the framing, long side up, with the 3 inch
spacer clearance at the top as shown in Figure
32, and nail into place.
(The Firestop/Spacer may also be installed over
the opening at the interior side of framing).
IMPORTANT
The vent termination is hot while
in operation and for a period of
time following the use of the fi re-
place. To prevent contact with hot
surfaces, we recommend the use
of a Termination Guard. See Items
12 and 13 on Page 32. This can be
purchased at your local dealer.
20
7"
(178)
12¹⁄₈"
(308 mm)
5¹⁄₈"
(130 mm)
Adapter
SV4.5RCH
6 to 48 inch Vent Section,
Telescopic vent section,
Elbow or Appliance Collar
Figure 32 -
INSTALLING SQUARE HORIZONTAL TERMINATION (SV4.5HT-2)
Use silicone caulking to seal
the top and sides of the
termination, up to the
underlayment, stucco, or
masonry wall surface.
Siding
Caulk
Last Vent Section.
Use Telescopic Vent
Section (SV4.5LA), If
Necessary
Caulk
SV4.5 HT-2
Termination
Stucco
For thicknesses greater
than 10", see Table 12
Venting Connection and Exterior Wall Recessing of the Horizontal Square
Figure 33
Termination (SV4.5HT-2).
Horizontal terminations have been designed to perform in a wide range of weather condi-
tions. Our terminations meet or exceed industry standards.
When selecting the locations of your horizontal terminations, do not place the termina-
tion where water from eaves and adjoining roofl ines may create a heavy fl ow of cascad-
ing water onto the termination cap. If the cap must be placed where the possibility of
cascading water exists, it is the responsibility of the builder to direct the water away
from the termination cap by using gutters or other means.
Take care to carefully follow the installation instructions for the termination, including
the use of silicone caulking where required.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
To help minimize water infiltration it is
recommended that the Firestop/Spacer
(SV4.5HF) be installed on the exterior
side of the wall.
10¹⁄₂"
(267mm)
Note: Centerline of Vent Piping is
NOT the Same as the Centerline of
the Framed Opening.
See Figure 13 on Page 11 for Min.
Distance to Base of Appliance.
Base of Appliance
Interior Surface of
Finished Wall
Maximum Extent of
Vent Run Sections
Relative to Exterior
Surface of Framing
Adapter
SV4.5RCH
SV4.5 HT-2
Termination
3"
(76 mm)
1"
(25.4 mm)
Maximum Wall Thickness
10 in. (254 mm)
Exterior Surface of Siding
Exterior Surface of
Framing
6 in. to 9-1/4 in.
(152 to 235 mm)
SV4.5 HT-2
Termination
1-1/4" Maximum Recess of
Square Termination
into Exterior Finishing Material

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sddv-40Sddv-35nmSddv-40nmSddv-35pmSddv-40pmSddv-35 series ... Show all

Table of Contents