Defrost (only applicable to the heating mode)
1. the intelligent defrost
In the heating mode, the electric control board checks and compares the temperature of indoor room and indoor coil
pipe after the compressor works for a while; judge whether the outdoor heat exchanger part is frosted or not according to
conditions such as the change of indoor coil pipe temperature; if it is judged as frosted, it automatically enters defrosting
process. When defrosting, close the indoor and outdoor blower fan and four-way valve.
2. Outdoor PCB for defrost.
In the heating mode, the unit defrost by outdoor control board:
①unit start defrost shall all meet the following conditions:
a、compressor continuous running over 7 minutes;
b、defrost relay shut off; (-5℃)
c、compressor cumulate running time over 50 minutes.;
②first defrost interval time is 50 minutes, later defrost interval time decided by last defrost time.
Defrost time(minute)
15
10--15
7--10
3--7
Next defrost interval time(minute)
30
40
60
70