10. Installation Instruction
10.1 Select the Best Location
10.1.1 Indoor Unit
x
There should not be any heat source or steam near
the unit.
x
There should not be any obstacles blocking the air
circulation.
x
A place where air circulation in the room is good.
x
A place where drainage can be easily done.
x
A place where noise prevention is taken into
consideration.
x
Do not install the unit near the door way.
x
Ensure the spaces indicated by arrows from the
wall, ceiling, fence or other obstacles.
x
Recommended installation height for indoor unit
shall be at least 2.5m.
10.1.2 Outdoor Unit
x
If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation
from the condenser is not obstructed.
x
There should not be any animal or plant which
could be affected by hot air discharged.
x
Keep the spaces indicated by arrows from wall,
ceiling, fence or other obstacles.
x
Do not place any obstacles which may cause a
short circuit of the discharged air.
x
If piping length is over the rated length,
additional refrigerant should be added as shown
in the table below:
Model
Piping
Rated
size
Length
Gas Liqui
(m)
d
RE9JKE 3/8" 1/4" 7.5
RE12JKE 3/8" 1/4" 7.5
RE15JKE 1/2" 1/4" 7.5
Example: If the unit is installed at a 10m distance,
the quantity of additional refrigerant should be 50 g.
...... (10-7.5) m x 20g/m = 50 g
Max
Min
Max
Elevatio
Piping
Piping
n (m)
Length
Length
(m)
(m)
5
3
15
5
3
15
5
3
15
11.1.3 Indoor/Outdoor Unit
Additional
Refrigera
nt (g/m)
20
20
20
*This illustration is for explanation purposes only.
The indoor unit will actually face a different way.
23