Locating Your Fireplace; Clearance To Combustibles; Mantels - Vermont Castings DVA4136 Installation Instructions And Homeowner's Manual

Top vent direct vent gas fireplace
Hide thumbs Also See for DVA4136:
Table of Contents

Advertisement

DVA4136 Series Direct Vent Gas Fireplace

Locating Your Fireplace

E
A
Y
D
Y
F
Fig. 2 Locate gas fireplace.
A - Flat on wall
B - Cross corner
D - *Room divider
E - *Flat on wall corner
Y - 6" minimum
Note (Fig. 2):
** Island (C) and Room Divider (D) installation is possible as
long as the horizontal portion of the vent system (X) does not
exceed 20' (6m). See details in manual Venting Section.
* When you install your fireplace in(D) Room divider or (E)
Flat on wall corner positions (Y), a minimum of 6" (152mm)
clearance must be maintained from the perpendicular wall and
the front side edge of the fireplace. See (Y) in Fig. 2.

Clearance to Combustibles

Top of Unit to Ceiling ................................ 36" (914 mm)
Appliance
Top .......................................................... 0" (0 mm)
Bottom ..................................................... 0" (0 mm)
Side ......................................................... 0" (0 mm)
Back ........................................................ 0" (0 mm)
Venting
Concentric sections of DV Vent
Top, bottom & sides .............................. 1" (25 mm)

Mantels

The height that a combustible mantel is fitted above the
fireplace is dependent on the depth of the mantel. This
also applies to the distance between the mantel leg (if
fitted) and the fireplace.
For the correct mounting height and widths refer to
Figures 3a and 3b.
The fitting of a bay window trim kit does not effect
the distances and reference points referred to in the
diagram and chart.
Noncombustible mantels and legs may be installed at
any height and width around the appliance.
When using paint or lacquer to finish the mantel,
such paint or lacquer must be heat resistant to
prevent discoloration.
6
B
X
C
X
B
LU584-T
Locating unit
C - **Island
12/18/02 djt
F - Chase installation
V
W
X
Y
Z
A
B
C
D
E
Bottom of Door Trim
Mantel Chart
Mantel Shelf
CFM146
Ref.
or Breast Plate
DV Mantel Chart
7/5/01 sta
Depth
V
10"
(254 mm)
W
8"
(203 mm)
X
6"
(152 mm)
Y
4"
(101 mm)
Z
2"
(51 mm)
Fig. 3a Combustible mantel minimum installation.
Black
Surround
Face
Side of
Combustion Chamber
CFM164a
Mantel Leg Chart
06/22/01 sta
Mantel
Ref.
Leg Depth
F
10"
(254 mm)
CFM170
G
8"
(203 mm)
DV Builder Front
View
H
6"
(152 mm)
I
4"
(101 mm)
J
2"
(51 mm)
Fig. 3b Combustible mantel leg minimum installation.
Noncombstible
Material
Standoff
3/4" (19 mm) Scribe
Moulding for use with
CFM Cabinets
Fireplace
Louvre Assembly
top
Top of Combustion
Chamber
CFM146
Mantel from Top
Ref.
of Comb. Chamber
A
19"
(483 mm)
B
17"
(432 mm)
C
15"
(381 mm)
D
13"
(330 mm)
E
11"
(279 mm)
3/4" (19 mm) Scribe Moulding
for use with CFM Cabinets
J
I
H
G
Mantel
Leg
K
L
M
N
O
CFM170
Mantel Leg FromSide
Ref.
of Comb. Opening
K
11¹⁄₂"
(292 mm)
L
9¹⁄₂"
(241 mm)
M
7¹⁄₂"
(191 mm)
N
5¹⁄₂"
(140 mm)
O
3¹⁄₂"
(89 mm)
10010270
F