Correlations
The following figure illustrates an example of Central Station/Remote Station Reporting using a
UDACT-F (Universal Digital Alarm Communicator/Transmitter). The UDACT-F transmits system
status to UL listed Central Station receivers via the public switched telephone network. It may be
mounted inside the MS-9600 cabinet using the BRKT-9600 mounting bracket or remotely in a
UBS-1F or ABS-8RF enclosure.
+24 VDC Nonresettable Power (TB3) Supervised and Power-limited
TB3
JP3
REMOVE TO
DISABLE
LOCAL
CHARGER
4XTM OPT BD
J10
Install 120Ω EOL resistor (P/N
71244) on TB1 Terminals 3 & 4, if
last or only device on EIA-485 line.
SHIELD
Notes:
1. Ferrite cores (P/N FBD-1) are recommended for all applications. Install around wires inside
cabinets near terminal blocks.
2. Recommended wire is 12 AWG to 18 AWG (0.75 to 3.25 mm
3. If shielded wire is used, connect only one end of the shield.
4. Conduit is recommended for external wire runs (consult local building codes).
5. Connect ground wire from Earth Ground terminal on the UDACT-F to a solid building earth
ground. Conduit alone will not provide a reliable earth ground.
6. UDACT-F may be located up to 6,000 feet (1,800 m) away from the host control panel.
MS-9600 PN 51335:E 7/9/03
ALARM TRBL SUPV
TB4
TB5
JP8
JP5
JP6
CUT TO
MONITOR 4XTM
J11
MS-9600 Main Circuit Board
Ferrite Core
+24V
1
GND
2
RS+
3
RS–
4
5
RS+
6
RS–
7
UDACT-F
Figure C.2 Central Station Service Using UDACT-F
NFPA Standard-Specific Requirements
ACS EIA-485 (TB6) Supervised and Power-limited
T
R
D
G
I
I
O
O
N
X
C
T
N
N
U
U
V
R
+
D
T
T
+ –
+
TB7
TB6
J10
J5
Ferrite
Core
shield
TB8
Phone Lines
(supervised)
Solid Earth
Ground
Connection
2
) twisted, shielded pair.
151