NFPA Standard-Specific Requirements
Monitor Module EOL resistor
K6
411UDAC
J4
AC wiring for 411UDAC/
FACP must be connected
to the same branch circuit.
MS-9600
150
NFPA Signaling Systems for Central Station Service (Protected Premises Unit)/
Remote Station
The following figure illustrates an example of Central Station/Remote Station
Reporting using a 411UDAC. The relay contacts from the MS-9600 may be used to trip
any dialer UL listed for Central Station/Remote Station Services. The UDACT-F may
also be used. Refer to Figure C.2, "Central Station Service Using UDACT-F," on page
151.
Notes:
1. Reference the 411UDAC Manual for additional information
2. Program the 411UDAC for slave operation
3. The MS-9600 must be programmed for AC Loss Reporting Delay This prevents
the transmission of a trouble on the loss of AC power
411UDAC Relay 2 Output (DACT Trouble)
Channel 2/Zone 2
Channel 1/Zone 1
2.2K
EOL
Channel 3/Zone 3
2.2K EOL
RELAY 1
RELAY 2
NAC
+12V PWR
ZONE 1
ZONE 2
ZONE 3
ZONE 4
NO NC C
NO NC C
B+ B-
+
-
B+ B-
B+ B-
B+ A+ A- B-
B+ B-
1 2 3 4 5 6 7 8 9 10
TB1
TB4
TB2
K5
COMM. FAIL
J1
AC PWR
BATT FAULT
SYS TRBL
ALARM
SUPV.
J7
TB3
BATTERY
EARTH AC-NEU AC-HOT
UL listed 2.2K EOLs (P/N 27070)
TB5
NC
C
NO
C
NC
NO
NO
NC
C
TB3
JP3
REMOVE TO
DISABLE
LOCAL
CHARGER
J10
Figure C.1 Central Station Service Using 411UDAC
Alarm
Trouble
Supervisory
Table C.1 411UDAC Connections to MS-9600
Note: The Monitor Module input, which is
being used to monitor the 411UDAC Relay
PH1
PH2
Output programmed for DACT Trouble
(requires optional 411RK Relay Kit), must
be programmed as 'Trouble' at the Fire-Lite
MS-9600. The 411UDAC must be
programmed as a Slave Communicator
(programming address 64 set to 2).
J8
J2
GND
FAULT
J3
Monitor Module Circuit Input
1 2 3 4 5 6 7 8 9
TB5
TB4
TB6
JP8
JP6
JP5
CUT TO
MONITOR 4XTM
4XTM OPT BD
J11
411UDAC
TB2-1
TB2-2
TB2-3
TB2-4
TB2-5
TB2-8
Correlations
Program the 411UDAC as follows:
Channel 1 - Normally Open Contact
Device (alarm)
Channel 2 - Host Panel Trouble
Channel 3 - Supervisory
Monitor Module
SLC Loop
TB7
TB8
MS-9600
TB5-3
TB5-1
TB5-6
TB5-5
TB5-9
TB5-7
MS-9600 PN 51335:E 7/9/03