14 Technical specifications

14.1 Technical specifications of GB162-boilers at sea level (0-4,000 ft.)

General specifications
Gas category
Rated thermal load
Rated heating capacity,
heating curve 176/140 °F (80/60 °C)
Rated heating capacity,
heating curve 122/86 °F (50/30 °C)
Boiler efficiency at max. capacity,
heating curve 176/140 °F (80/60 °C)
Boiler efficiency at max. capacity,
heating curve 122/86 °F (50/30 °C)
CSA Output
De-ration altitudes 2,000 - 4,000 ft.
AFUE at 80/180 °F (27/82 °C)
BTS 2000 at 80/180 °F (27/82 °C) part. load
BTS 2000 at 80/180 °F (27/82 °C) full load
Heating
Maximum flow temperature
Maximum working pressure (boiler)
Minimum water circulation volume
Flow temperature
Resistance at ΔT = 20 K
Heating circuit volume of heat exchanger
Pipe connections boiler, without pump group.
Gas connection
Heating water connection
Condensate connection
Flue gas values
Condensate quantity at 104/86 °F (40/30 °C) Gal/h (L/h)
pH value of condensate
Flue gas mass flow rate, full load
Flue gas temperature 176/140 °F
(80/60 °C), full load
Flue gas temperature 176/140 °F
(80/60 °C), partial load
Flue gas temperature 122/86 °F
(50/30 °C), full load
Flue gas temperature 122/86 °F
(50/30 °C), partial load
CO
content at full load
2
Free fan feed pressure
Flue gas connection
Ø Flue gas system, room-air dependent
Ø Flue gas system, room-air independent
Electrical data
Tab. 24 Technical specifications of GB162-boilers at sea level
Logamax plus GB162- 80/100 kW - Subject to modifications resulting from technical improvements!
unit
GB162-80 (NG)
Natural gas
btu/h
72,000-290,000 62,000-270,000 72,000-333,000 62,000-315,000
btu/h
64,100-255,200 55,200-237,600 64,100-293,000 55,200-277,200
btu/h
71,300-281,300 61,400-261,900 71,300-326,300 61,400-308,700
%
88
%
97
btu/h
261,000
% / 1,000 ft.
2.3
93.8
n/a
n/a
°
°F(
C)
psi (bar)
Gal/h (l/h)
°
°F(
C)
86-180 (30-82), can be set on the BC10 basic controller
psi (bar)
3.26 (225)
Gal (L)
in
in
G1½" union nut with female thread enclosed
in (mm)
2.4 (9.0)
pH
g/s
35.3
°F(°C)
153 (67)
°F(°C)
142 (61)
°F(°C)
118 (48)
°F(°C)
93 (34)
%
9.3± 0,2%
" w.c. (Pa)
0.602 (150)
in (mm)
in (mm)
Technical specifications
GB162-80 (LP) GB162-100 (NG) GB162-100 (LP)
Propane
Natural gas
243,000
295,000
2.2
2.1
93.9
n/a
n/a
96.1
n/a
90.8
180 (82)
50 (3.6)
0
4.57 (315)
1.3 (5.0)
Rp1"
Ø 1¼" (32)
2.85 (10.8)
approx. 4.1
149 (65)
169 (76)
136 (58)
142 (61)
114 (46)
124 (51)
88 (31)
96 (34)
9.6
9.4± 0,2%
0.883 (220)
Ø 4" (100)
Ø 4" (100)/ 4"(100) parallel
14
Propane
88
98
279,000
2.0
n/a
96.1
90.8
44.9
165 (63)
136 (58)
120 (49)
88 (31)
9.7
65