Installation space
Air inlet
L2
Air
inlet
Air outlet
Case
I
Distance
open
L1
L2
300
150
L3
Installation where the area with strong winds.
Install the unit so that the air outlet section of the unit must NOT be faced toward wind direction.
Installation
Fix the unit in a proper way according to the condition of a place where it is installed by referring to the
following .
(a) Concrete foundation
Anchor bolt
Install the unit so that the angle of inclination must be less than 3 degrees.
Installation sketch of outdoor unit
L3
500
(Servicing
space)
L1
II
open
0
300
Unit
Concrete foundation
780
>a__WcU[S^ <[c >a`V[e[a`Wc
Note :
(1). Fix the parts with screws
(2).Don't intake the strong wind directly to the outlet air
-flow hole.
(3).A one meter distance should be kept from the unit top
(4).Don't block the surroundings of the unit with sundries
Unit: mm
III
500
open
150
(b) Foundation anchor
To fix by bolts
Power Wiring Terminal
Power Wiring
Distribution Hole
-184-
NO
Wind direction
Unit
Concrete foundation
Anchor bolt