Ferroli DOMINA 102 DGT Installation, Servicing And User Instructions Manual page 18

Copper wall-mounted combination, gas fired boiler for central heating and domestic hot water production, fan assisted, room sealed compartment, electronic flame ignition and control
Table of Contents

Advertisement

For further accessories please refer to:
"Flue system manual for room sealed boiler"
Example of calculation for wall inlet/outlet
with 2 pipe system
maximum total flue length: 50 metres
13 m
7
6
3.04.3 Example of other installation with two pipe systems
Example of wall inlet/outlet
2 pipe application
18
DOMINA 102 DGT
13 m
5 1
2
Fig. 19
Example of direct roof flue outlet
Fig. 20a
Attention:
Remove the flue diaphragm.
The flue + air Pipes must have a 3% drop away
from the boiler to outside
3
°
REF.
N
OF PIECES DESCRIPTION
1
1
2
13
3
1
5
1
6
13
7
1
and wall air inlet
Fig. 20b
Air bend 80 mm R/D = 0,75
Horizontal air pipe
Air wall terminal
Flue bend 80 mm R/D = 0,75
Horizontal flue
Air wall terminal outlet flue
TOTAL
Example of roof inlet/outlet
LENGTH OR
REDUCTION
1,5 m
13,0 m
2,0 m
2,5 m
26,0 m
5,0 m
50,0 m