Installation Dimensions - Schwank SET - SETU Owner's Manual

Two stage low intensity tube type infrared heaters
Hide thumbs Also See for SET - SETU:
Table of Contents

Advertisement

FIGURE 21 BURNER DIMENSIONS
FIGURE 22 HANGER SPACING / LENGTH - AIR INTAKE TO VENT END
*

POSITION BURNER END HANGER 4 INCHES (10 CM) FROM BURNER

LOCATE SYSTEM HANGERS NO LESS THAN 6 INCHES (15 CM) AND NO MORE THAN 24
INCHES (61 CM) FROM TUBE COUPLING
* ANGLE BURNER SUPPORT CHAIN BACK OVER BURNER - ALLOWS TUBE SYSTEM EXPANSION
Tube
Length
'L' = center air intake to vent end
20'
20'-11 3/4" ; 251 3/4"
30'
30'-7 3/4"
40'
40'-3 3/4"
SET(U)-F / ITT(U)-F Manual
IM091221
RD: FEB 2014
RL: 8B
;
628 cm
; 367 3/4"
;
934 cm
; 483 3/4"
; 1229 cm
Tube
Length
'L' = center air intake to vent end
50'
49'-11 3/4" ; 599 3/4"
60'
59'-7 3/4"
42
; 1523 cm
; 715 3/4"
; 1818 cm