22. TROUBLESHOOTING GUIDE - HEATER OPERATION
WARNING
SEQUENCE OF EVENTS (also see DSI Troubleshooting previous page)
APPLY 120 VOLTS
SET THERMOSTAT TO CALL FOR HEAT
COMBUSTION AIR BLOWER STARTS
YES
AIR PROVING SWITCH HAS CLOSED 24
VOLTS IS PRESENT AT "PSW"
CONTROL.
YES
BLOCKED FLUE SWITCH IS CLOSED
24 VOLTS IS PRESENT AT "TH" AT DSI
CONTROL.
YES
SPARK IGNITER / SENSOR
YES
24V TO GAS VALVE
CONTINUED
Improper adjustment, alteration, service or maintenance can
cause property damage, injury or death. This heater must be
NO
REMEDY 120 VOLTS SUPPLY FAULT
CHECK 120V TO DSI AT "L1"
NO
CHECK 120V OUT AT "IND" FROM DSI TO BLOWER
NO
FAULTY RELAY SWITCH IN DSI — REPLACE DSI
CHECK TUBING TO SWITCH IS CONNECTED AND
NO
AT DSI
CHECK AIR PRESSURE WITH MANOMETER
CHECK FOR OBSTRUCTION IN THE AIR INTAKE
CHECK INTEGRITY OF SWITCH
CHECK TUBING TO SWITCH IS CONNECTED AND
NO
CHECK AIR PRESSURE WITH MANOMETER
CHECK INTEGRITY OF SWITCH
CHECK FOR AND REMEDY ANY OBSTRUCTION IN
CHECK DSI CONTROL FUSE FOR CONTINUITY
NO
VISIBLY CHECK IF IGNITER IS SHORTING OUT
CHECK GROUND WIRING
REMOVE AND INSPECT IGNITER AND LEAD
CHECK BOOT OF THE IGNITION CABLE FOR SIGNS
IF "YES" ... TAKE PROTECTIVE ACTION TO SHIELD
CHECK CERAMIC INSULATOR AND CAP
CHECK SPARK GAP SETTING IS 3/16" (ADJUST BY
PERFORM IGNITION LEAD TEST (See SPARK IGNI-
GOOD SPARK.....REPLACE IGNITER
NO SPARK/OR WEAK.....REPLACE CONTROL
37
NOT BLOCKED OR KINKED
REPLACE DEFECTIVE BLOWER
REPLACE DEFECTIVE SWITCH
NOT BLOCKED OR KINKED
REPLACE DEFECTIVE SWITCH
THE VENT / TUBE
OF MELTING OR OVERHEATING
CABLE AND BOOT FROM EXCESSIVE TEMPERA-
TURE; REPLACE ANY DEFECTIVE COMPONENT
MOVING THE GROUND PRONG ONLY)
TION CIRCUIT INSTRUCTIONS—Section 22)
SET(U)-F / ITT(U)-F Manual
IM091221
RD: FEB 2014
RL: 8B