Spark Igniter Adjustment - Schwank SET - SETU Owner's Manual

Two stage low intensity tube type infrared heaters
Hide thumbs Also See for SET - SETU:
Table of Contents

Advertisement

SPARK IGNITER ADJUSTMENT

Use the following diagram to check the Igniter gap. If the gap is incorrect all adjustments
should be made to the GROUND PRONG/PIN ONLY! DO NOT BEND THE IGNITER
PRONG!!!!
USE THE BLACK BARS BELOW AS A GUIDE FOR AD-
JUSTMENT.
USE THE BARS THAT COINCIDE WITH
THE FORMAT & SIZE OF THIS PUBLICATION .
IF
this manual is in
"booklet" format
8.5" x 11"
(pages folded in half)
then use these bars
OR
IF this manual is printed
8.5" x 11" "full page" format
use these bars
SERVICE CHECKS
Flame current passes through the flame from
the sensor to ground. The minimum flame cur-
rent necessary to keep the system from lock-
out is 0.7 microamps. To measure flame cur-
rent, connect an analog DC microammeter to
the FC- FC+ terminals per figure at right.
Meter should read 0.7 µA or higher. If the me-
ter reads below "0" on scale, meter leads are
reversed. Disconnect power and reconnect
meter leads for proper polarity.
3/16"
1/4"
1/4"
3/16"
Multipurpose Meter
35
ADJUST
Use Microamp
scale
SET(U)-F / ITT(U)-F Manual
IM091221
RD: FEB 2014
RL: 8B