McQuay MWM Service Manual Book page 52

Hide thumbs Also See for MWM:
Table of Contents

Advertisement

Inverter Outdoor Unit
Model
SLX 10/15/20/25C/CR
MSV 25/35A
MSX 20/25/30A/AR
Normal running / compressor running RED LED blinking
No. of Blinks
1
2
3
4
5
6
7
8
Compressor stopped RED LED blinking
No. of
Faulty Indication
Blinks
1
Outdoor ambient sensor error
2
Outdoor coil sensor error
Outdoor discharge sensor error /
3
compressor overheat
4
DC compressor feedback error
5
Communication error
6
Over current error
7
No load
8
Over / under voltage
9
DC compressor start failure
10
Cooling overload
11
Defrost
12
IPM protection
13
Read EEPROM error
14
Write EEPROM error
Blinking Indication
Normal running, with no limitation
Voltage limit
Cooling unit: outdoor coil temperature limit
Heating unit: indoor coil temperature limit
Total current limit
Discharge temperature limit
Cooling unit: indoor coil temperature limit
Indoor fan control
Outdoor frequency adjustment
No. of
Faulty Indication
Blinks
15
DC fan motor feedback error
16
AC peak current error
17
Outdoor suction sensor error
18
None
19
DC compressor speed control error
20
None
21
Outdoor suction pipe A sensor error
22
Outdoor suction pipe B sensor error
23
Outdoor suction pipe C sensor error
24
Outdoor suction pipe D sensor error
31
Communication error with indoor A
32
Communication error with indoor B
33
Communication error with indoor C
34
Communication error with indoor D
51