Master settings
Only if multiple units have been connected to a single
control panel
all units config-
ured as normal
units
external control
only connected
input
unit responds
automatic tem-
each unit is
perature control
independently
controlled
2.7.6 Multiple units operated from one control panel
A maximum of eight units may be connected to a single
control panel.
Units are daisy chained using Biddle control cables and
Connectors
and .
The total length of the control cables between connected
units may not be any longer than 30 m.
Configure any one unit as a master. The sequence of the
connected units is not important.
Connect the control panel and external control compo-
nents to the master unit.
Note:
n
Do NOT remove the external control input bridges
on the other units.
See also:
2.7.3 "External control input" on page 19
2.7.5 "Unit settings" on page 20
Units with two control PCBs
Only the following types: DF S-250-E, M-250-E,
L-250-E
These units have two control PCBs that each control a part of
the unit. The control PCB on the connection side has been
configured as master on delivery.
en
I
NSTALLATION
one unit config-
ured as a master
unit
all units follow
the master
all units are
controlled by
the master
en-21