CONSTRUCTION, SPECIFICATIONS & DATA

Air Flow

MOVINCOOL CLASSIC PLUS 14 SERVICE
1.

Basic Construction

The MovinCool Spot Cooling System is
compact in construction because the con-
denser and the evaporator are enclosed in
one unit. The interior is divided into three
sections. The upper front face is equipped
with the evaporator, while the lower front face
contains the drain tank. The rear section
contains the condenser, the compressor and
the control box.
2.
Air Flow
Air drawn from the right side face passes
through the condenser which extracts the
heat. This hot air is blown out through the
upper exhaust air duct. Air taken in from the
front face is cooled by the evaporator and then
blown through the cool air duct which can be
turned in any direction. All the air inlets are
equipped with filters, while the exhaust air duct
is protected by wire mesh.
3.

Compressor and Fans

The compressor is hermetically sealed. A two-
speed fan motor is used with two centrifugal
fans to draw air across the evaporator and
condenser.
4.

Drain Tank

The capacity of the drain tank is 5.0 gallons
(19 liters). The unit is equipped with a "Tank
Full" LED and a device to automatically stop
the operation of the unit when the drain tank
reaches a level of approximately 4.0 gallons
(15 liters).