Clearance Specifications - Jøtul F 118 CB Installation And Operating Instructions Manual

Table of Contents

Advertisement

USA/Canada
Jøtul F 118 Clearance Specifications
Measure clearances from the combustible surface to the closest stove surface.
STOVE
CLEARANCES
Stove - No Heat Shield,
Single Wall Pipe
Stove - Rear & Side H/S
with Single Wall Pipe
Stove - Rear & Side H/S
with Double Wall Pipe
Use of Side Heat Shield is not required to obtain rear clearance using Rear Heat Shield only.
Use of Rear Heat Shield is not required to obtain side clearance using Side Heat Shield only.
Both stove heat shields required for reduced corner clearance.
Vertical Chimney
Connector Clearance
Single Wall Pipe
Double Wall Pipe
Horizontal
Connector Clearance
Single Wall Connector
Double Wall Pipe
K* : As tested, no clearance reduction is obtained with wall shielding
Figure 14. Minimum Wall Shield sizes, centered on stove.
Wall Protection construction must follow NFPA 211 or CAN/CSA guideliines.
Corner wall protection extends 38" from corner.
12
UNPROTECTED SURFACE
INSTALLATION
SIDE
REAR
A
B
35"/ 89 cm
9"/ 23 cm
G
H
18"/ 45.7 cm 4"/ 10.2 cm 12"/ 30.5 cm 12.5"/31.7 cm
M
N
18"/ 45.7 cm
3"/ 7.6 cm 12"/ 30.5 cm 12.5"/ 31.7 cm
UNPROTECTED SURFACE
13" / 33 cm
7" / 18 cm
UNPROTECTED SURFACE
18" / 45.7 cm
6" / 15 cm
PROTECTED SURFACE INSTALLATION
PER NFPA211 OR CAN/CSA -B365-M93
CORNER
SIDE
C
D
26"/ 66 cm
29.5"/ 75 cm
I
J
O
P
per NFPA211 or CAN/CSA-B365-M93
PROTECTED SURFACE
per NFPA211 OR CAN/CSA-B365-M93
Use mfg's specification
REAR
CORNER
E
F
8.5"/21.5 cm 22"/ 56 cm
K*
L
4.5"/ 11.4 cm 9.5"/ 24 cm
Q
R
3.5"/ 8.9 cm 8.5"/ 21.6 cm
PROTECTED SURFACE
12.5" / 31.7 cm
7" / 18 cm
12.5" / 32 cm