Chimney Requirements; Masonry Chimneys - Jøtul F 118 CB Installation And Operating Instructions Manual

Table of Contents

Advertisement

• For the best performance, the chimney connector
should be as short and direct as possible, including no
more than two 90° elbows.
• The maximum vertical run of single wall stovepipe
should not exceed 10 ft. (305 cm).
• The maximum horizontal run should not exceed 3 ft.
(92 cm) with a 1/4" rise per foot. Under no circumstance
should horizontal pipe be allowed to slant down toward
the chimney.
• No part of the chimney connector may pass through an
attic or roof space, closet or other concealed space, or
through a floor or ceiling. All sections of the chimney
connectors must be accessible for cleaning. Where
passage through a wall or partition of combustible
construction is desired, the installation must conform
with NFPA 211 or CAN/CSA-B365, and is also addressed
in this manual.
• Do not connect this stove to a chimney flue serving
another appliance.

2.0 Chimney Requirements

There are two types of approved chimneys:
1. A code-approved masonry chimney with a ceramic tile
or listed steel flue liner.
2. A prefabricated chimney complying with the
requirements for Type HT (2100°F) chimneys per UL
103 or ULC S629.
The chimney size should not be less than the cross-
sectional area of the flue collar, and not more than three
times greater than the cross-sectional area of the flue
collar.
When selecting a chimney type and the location for the
chimney in the house, keep this in mind: It is the chimney
that makes the stove work - not the stove that makes the
chimney work. This is because a chimney actually creates a
suction, called "draft" which pulls air through the stove.
Several factors affect draft: chimney height, cross-sectional
area (size), and temperature of the chimney, as well as the
proximity of surrounding trees or buildings.
A short exterior masonry chimney will give the poorest
performance because it will be difficult to warm the flue
and sustain the temperatures necessary to maintain draft
strength. In extremely cold climates, it may be necessary to
reline the chimney or extend the height to help establish
draft.
A tall, interior masonry chimney is easier to keep warm
and will perform the best under a variety of weather and
environmental conditions.
The following guidelines give the necessary chimney
requirements based on the national code (ANSI-NFPA
211 for the US. And CSA CAN-B365 for Canada). However,
many local codes differ from the national code to take
into account climate, altitude, or other factors. Your local
building inspector is the final approving authority. Consult
them prior to installation.
Do not connect the stove to any air distribution duct or
system.

2.1 Masonry Chimneys

Follow these guidelines when installing the Jøtul F 118
into a masonry fireplace:
• The masonry chimney must have a fireclay liner
or equivalent, with a minimum thickness of 5/8"
(14 mm) and must be installed with refractory mortar.
There must be at least 1/2" (12.7 mm) air space between
the flue liner and chimney wall.
• The fireclay flue liner must have a nominal size of
8" X 8" (20 cm x 20 cm), and should not be larger
than 8"X 12" (20 cm x 30 cm). A round fireclay liner
must have a minimum inside diameter of 6" (15
cm) and maximum inside diameter of 8" (20 cm).
A larger chimney should be relined with an appropriate
code approved liner.
USA/Canada
7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents