Operating Mode Description - Uninterruptible Power Supplies Online UPS 1K User Manual

Rack/tower online ups 1k/1.5k/2k/3k
Table of Contents

Advertisement

3-6. Operating Mode Description

Operating
Description
mode
Online mode When the input voltage is within
acceptable range, UPS will provide
pure and stable AC power to output.
The UPS will also charge the battery at
online mode.
ECO mode
When the input voltage is within
(Efficiency
setting range (±3%Vo max), UPS will
Corrective
bypass voltage to output for energy
Optimizer)
saving. PFC and INVERTER are still
active at this mode.
AECO mode
When the input voltage is within
(Advanced
setting range (±3%Vo max), UPS will
Efficiency
bypass voltage to output for energy
Corrective
saving. PFC and INVERTER are off at
Optimizer)
this mode.
Frequency
When input frequency is within 40 Hz
Converter
to 70 Hz, the UPS can be set at a
mode
constant output frequency, 50 Hz or
60 Hz. The UPS will still charge
battery under this mode.
Battery
When the input voltage is beyond the
mode
acceptable range or power failure and
alarm is sounding every 4 second,
UPS will backup power from battery.
Bypass
When input voltage is within
mode
acceptable range but UPS is
overload, UPS will enter bypass mode
or bypass mode can be set by front
panel. Alarm is sounding every 10
second.