Rayburn XT- Oil Installation Instructions Manual

Rayburn XT- Oil Installation Instructions Manual

Oil (k p/f) series

Advertisement

Installation
Instructions
XT - Oil (K P/F)
For use in GB and IE
DESN 514112 B
Remember, when replacing a part on this appliance, use only spare parts that you can be assured conform the safety and
performance specification that we require. Do not use reconditioned or copy parts that have not been clearly authorised
by AGA.
PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLING THIS APPLIANCE
raywarranty@aga-web.co.uk
10/13 EINS 514137

Advertisement

Table of Contents
loading

Summary of Contents for Rayburn XT- Oil

  • Page 1 Installation Instructions XT - Oil (K P/F) For use in GB and IE DESN 514112 B Remember, when replacing a part on this appliance, use only spare parts that you can be assured conform the safety and performance specification that we require. Do not use reconditioned or copy parts that have not been clearly authorised by AGA.
  • Page 2: Table Of Contents

    Contents SECTION CONTENTS PAGE CONSUMER PROTECTION HEALTH & SAFETY TECHNICAL DATA SITE REQUIREMENTS INTRODUCTION REGULATIONS LOCATION OIL PIPE LINE OIL STORAGE SINGLE & TWO PIPE SYSTEMS 7 - 8 FLUE SYSTEM 9 - 11 FLUE TERMINAL LOCATIONS AIR SUPPLY ELECTRICAL SUPPLY INSTALLATION CLEARANCES REQUIREMENTS...
  • Page 3: Consumer Protection

    Consumer Protection As responsible manufacturers we take care to make sure that our products are designed and constructed to meet the required safety standards when properly installed and used. IMPORTANT NOTICE: PLEASE READ THE ACCOMPANYING WARRANTY. Any alteration that is not approved by AGA could invalidate the approval of the appliance, operation of the warranty and could affect your statutory rights.
  • Page 4: Technical Data

    PLEASE NOTE: IT IS ADVISABLE TO CHECK THE ACTUAL SIZE/WIDTH OF YOUR APPLIANCE BEFORE FINALLY FIXING ANY KITCHEN UNITS SINCE ENAMELLED CAST DESN 514170 B IRON CAN VARY IN SIZE. TECHNICAL DATA Oil Inlet R1/4 (1/4” BSP Taper Ext) Unpacked Weight of Appliance - 350 Kg Electrical Supply 230V ~ 50Hz 3 amp Fused Firing Rate - 1.44 l/h...
  • Page 5: Site Requirements

    Site requirements INTRODUCTION LOCATION The Rayburn is a floor standing cooker, fired by a Appliance Hearth. The surface temperature of the floor pressure jet oil burner. below the appliance does not exceed 100°C. The constructional hearth described in current Building IMPORTANT Regulations does not apply.
  • Page 6: Oil Pipe Line

    Site requirements OIL PIPE LINE OIL STORAGE SEE FIG 2 & 3 The oil supply connection between the storage tank and The minimum recommended oil tank size is 1400 litres, the oil pipe should be run in copper or steel pipe with a Mild Steel Tanks should be to BS.
  • Page 7 Site requirements DESN 514167 C Single Pipe oil system DESN 514169 B Two Pipe oil system H METRES -3.0 -3.5 -4.0 MAXIMUM LENGTH 10mm OD (METRES) FIG. 2...
  • Page 8 Site requirements Deaerator Oil System FIG. 3 DESN 514168 B ONE & TWO PIPE SYSTEMS SEE FIG. 4 The cooker as delivered is ready to be used on a one pipe system. To convert to a two pipe system. (See Fig. 4) Sections:- BURNER ACCESS, steps 1 to 3, BURNER REMOVAL, steps 1 to 5...
  • Page 9 Site requirements FLUE SYSTEM The flue can be to the left or right of the appliance. The cooker is supplied with the flue pipe to the left, this can be adjusted to suit the installation. FLUE DIRECTION - EXIT TO THE LEFT 1.
  • Page 10 Site requirements FLUE DIRECTION - EXIT TO THE RIGHT Follow previous instructions in FLUE SYSTEM, Steps 1 to 4. Reposition the flexible tube from the oven vent down the back of the oven. 5. Smear sealant on the end of the manifold and replace the bend.
  • Page 11: Flue System 9

    Site requirements FLUE SYSTEM The flue system used on this appliance must be provided by AGA and must be installed in accordance with the instructions and standards. A maximum flue of 5 metres and 5 bends can be used (including horizontal length on the terminal). Any upwards vertical runs must be immediate to the appliance to a maximum of 3 metres.
  • Page 12 Site requirements - Flue terminal location FIG. 12 - Location of flue terminal DISTANCES STATED ARE MINIMUM ALLOWABLE REQUIREMENTS A DIRECTLY BELOW AN OPENING, AIR 600mm K VERTICALLY FROM A TERMINAL 1500mm BRICK, OPENING WINDOW etc. ON THE SAME WALL B HORIZONTALLY TO AN OPENING, AIR 600mm L HORIZONTALLY FROM A TERMINAL ON...
  • Page 13: Air Supply

    Site requirements AIR SUPPLY AIR SUPPLY Detailed recommendations for air supply are given in the The appliance can only be installed in a room which Building Regulations, and in BS 5410: Part 1. The meets the ventilation regulations in force. But, in any following notes are intended to give general guidance.
  • Page 14: Electrical Supply

    Site requirements ELECTRICAL SUPPLY Wiring external to the appliance must be installed in accordance with current National Wiring Regulations and any local regulations which apply. The appliance is supplied for 230 Volt ~ 50Hz and a fuse rating of 3 amps. The method of connection to the mains supply should facilitate complete electrical isolation of the appliance, by the use of a fused double pole switch having a contact...
  • Page 15: Installation Requirements

    Installation requirements CLEARANCES The appliance is floor mounted. The space in which the appliance is to be fitted must have the following minimum dimensions. Between wall or unit and LH side of - 10mm appliance top plate Between wall or unit and RH side of - 10mm appliance top plate SHOULD THE WALL PROJECT BEYOND THE FRONT...
  • Page 16: Site Location

    Installation requirements SITE LOCATION 1. Check that the hearth is level, then remove the appliance from its transit wooden pallet, and position it with its back against the wall and in its intended position for flue connection. 2. Connect and terminate the flue system in accordance with these instructions.
  • Page 17 Installation Requirements INSTALLATION 1. Cut out card template from packaging and affix to wall. 2. Cut ø60mm hole in the wall for the flue pipe (See Fig. 16). 3. Drill 4 wall fixing holes through template (1 in each corner). (See Fig. 16). 4.
  • Page 18: Pcb Connections

    Installation Requirements PCB CONNECTIONS EXTERNAL CONNECTIONS : FAN CONNECTIONS - AT TERMINAL MAINS CONNECTIONS FIG. 20...
  • Page 19: Commissioning Instructions

    Commissioning Instructions NOTE: SMOKE/SMELL EMITTED DURING INITIAL USAGE. During Initial usage of operation of the cooker, smoke/smell may be emitted and is normal and not a fault with the appliance, it is therefore advisable to open doors and or windows to allow for ventilation. BURNER ACCESS SEE FIG.
  • Page 20: Overheat Safety Thermostat

    Commissioning Instructions ELECTRICAL CHECK Checks to ensure electrical safety should be carried out by a competent person. OVERHEAT SAFETY THERMOSTAT IMPORTANT NOTE: This appliance is fitted with an overheat thermostat which has a manual reset button. If the overheat stat trips, the cooker will not operate, until the button has been pushed-in (reset).
  • Page 21: Flue Safety Device

    Commissioning Instructions FLUE SAFETY DEVICE This thermostat is a safety cut-out device which will operate under adverse wind or a blocked flue condition. It is a manually reset device which can be reset by pressing in the centre. FIT PRESSURE GAUGE SEE FIG.
  • Page 22: Set Combustion Air

    Commissioning Instructions SET COMBUSTION AIR SEE FIG.25 & 26 The air control of the burner is factory pre-set, however small adjustments may be necessary to suit the site conditions. IMPORTANT: Ensure that the bottom louvred plinth is in place during combustion setting procedures and the outer door is closed.
  • Page 23: Ancillary Controls Check

    Commissioning Instructions ANCILLARY CONTROLS CHECK INSTRUCT THE USER Before leaving the site, check that the operation of cooker 1. Advise the User that, for continued efficient and safe timer and thermostat are capable of controlling the burner operation of the appliance, it is important that adequate correctly.
  • Page 24: Wiring Diagram - Appliance

    Wiring Diagram WIRING DIAGRAM - APPLIANCE FIG. 27...
  • Page 25 Single Channel Programmer USING A SINGLE CHANNEL OPTIONAL PROGRAMMER IN CONJUNCTION WITH THE RAYBURN 400K PX (P/F) ONLY 1. Always use the same isolating switch for both the cooker and programmer. Ideally: always use the supply connections on the appliance.
  • Page 28 With AGA Rangemaster’s policy of continuous product improvement, the Company reserves the right to change specifications and make modifications to the appliance described at any time. Manufactured by AGA Rangemaster Station Road Ketley Telford Shropshire TF1 5AQ England www.rayburn-web.co.uk www.agacookshop.co.uk...

This manual is also suitable for:

Xt- oil k pXt- oil k fXt series

Table of Contents