Ruud AP15318 Use & Care Manual page 9

Outdoor gas tankless water heater
Table of Contents

Advertisement

V VENT TERMINAL
Horizontal  Vent  Terminal  Location
The  following  information  should  be  used  for  determining  the  proper  location  of  the  vent  terminal  
for  indoor  and  outdoor  tankless  water  heaters.
A=       Clearance  above  grade,  veranda,  
porch,  deck  or  balcony.
B=       Clearance  to  window  or  door  that  
may  be  opened.
C=       Clearance  to  permanently  closed  
window.
D=       Vertical  Clearance  to  ventilated  
soffit  located  above  the  terminal  
within  a  horizontal  distance  of  2  
feet  (61  cm)  from  the  center  line  of  
the  terminal.
E=    Clearance  to  unventilated  soffit.
F=    Clearance  to  outside  corner.
G=    Clearance  to    corner.
H  =     Clearance  to  each  side  of  center  line  
extended  meter/regulator  assembly.  
above  
I  =       Clearance  to  service  regulator  vent  
outlet.
J  =       Clearance  to  nonmechanical  air  
supply  inlet  to the combustion  
air  inlet  to  any building  or  other  
appliance.
K  =       Clearance  to  mechanical air  supply  
inlet.
L  =       Clearance  above  paved  sidewalk  or  
paved  driveway located on  public
property.
M  =     Clearance  under  veranda,  porch,  
deck  or  balcony.
1   In  accordance  with  current  CSA-­B149.1  Installation  Codes.
2   In  accordance  with  current   A NSI  Z223.1/  NFPA  54  National  Fuel  Gas  Code.
†   A  vent  shall  not  terminate  directly  above  a  sidewalk  or  paved  driveway  that  is  located  between  two  single  family
 
dwellings  and  serves  both  dwellings.
*   For  clearances  not  specified  in   A NSI  223.1/NFPA  54  or  CSA-­B149.12,  one  of  the  following  shall  be  indicated:
 
a)  
A  minmum  clearance  value  determined  by  testing  in  accordance  with  section  2.20,  or;;
 
b)  
A  reference  to  the  following  footnote:    "Clearance  in  accordance  with  local  installtion  codes  and  the  require-­
 
 
ments  of  the  gas  supplier."
AP15318 tankless 10 30 09.indd 9
X AIR SUPPLY INLET
Canadian Installations
1
Outdoor
12  inches  (30  cm)  above  anticipated  
snow  level.
6  inches  (15  cm)  for  appliances  <  10,000  
Btuh  (3  kW),  12  inches  (30  cm)  for  
appliances  >  10,000  Btuh  (3kW)  and  <  
100,000  Btuh  (30kW),  36  inches  (91  cm)  
for  appliances  >  100,000  Btuh  (30kW).
*
*
*
*
*
3  feet  (91  cm)  within  a  height  15  feet  
(4.57  m)  above  the  meter/regulator  
assembly.
3  feet  (91  cm)
 
6  inches  (15  cm)  for  appliances  <  
10,000  Btuh  (3  kW),  12  inches  (30  cm)  
for  appliances  >  10,000  Btuh  (3kW)  
and  <  100,000  Btuh  (30kW),  36  inches  
(91  cm)  for  appliances  >  100,000  Btuh  
(30kW).
6  feet  (1.83  m)
7  feet  (2.13m)  †
Not   A llowed
AREA WHERE TERMINAL IS NOT PERMITTED
US Installations
2
Outdoor
12  inches  (30  cm)  above  anticipated  
snow  level.
6  inches  (15  cm)  for  appliances  <  
10,000  Btuh  (3  kW),  9  inches  (23  cm)  
for  appliances  >  10,000  Btuh  (3kW)  
and  <  50,000  Btuh  (15kW),  12  inches  
(30  cm)  for  appliances  >  50,000  Btuh  
(15kW).
*
*
*
*
*
*
*
6  inches  (15  cm)  for  appliances  <  10,000  
Btuh  (3  kW),  9  inches  (23  cm)  for  
appliances  >  10,000  Btuh  (3kW)  and  <  
50,000  Btuh  (15kW),  12  inches  (30  cm)  
for  appliances  >  50,000  Btuh  (15kW).
3  feet  (91  cm)  above  if  within  10  feet  
(3  m) horizontally.
*  
Not   A llowed
9
11/9/2009 3:17:35 PM