Ruud AP15318 Use & Care Manual page 13

Outdoor gas tankless water heater
Table of Contents

Advertisement

Installing  the  water  heater:
Pressure
Relief
Valve
Union  
Water  
Shutoff  
Valve  
Relief  
Valve  
Hot  Water  
Discharge  
Supply  
Line  
Outlet  
Notice:  The  above  illustrates  
a  pressure-­only  relief  valve.  If  
local  codes  require  a  combination  
temperature  and  pressure  relief  
valve  be  installed,  an  extension  
piece  may  be  needed  to  ensure  that  
the  valve  probe  is  not  directly  in  
the  flow  path  of  the  water.  
AP15318 tankless 10 30 09.indd 13
Relief  Valve
A  new  pressure  relief  valve,  complying    
with  the  Standard  for  Relief  Valves  and  
Automatic  Gas  Shut-­Off  Devices  for  Hot  
Water  Supply  Systems,   A NSI  Z21.22/  
CSA  4.4,  must  be  installed  at  the  hot  water  
outlet  connection  of  the  water  heater  at  
the  time  of  installation.  Local  codes  shall  
govern  the  installation  of  relief  valves.
For  safe  operation  of  the  water  heater,  be    
sure  that:
G     The  pressure  rating  of  the  relief  valve  
must  not  exceed  150  psi  (1034  kPa),  the  
maximum  working  pressure  of  the  water  
heater  as  marked  on  the  rating  plate.
Cold  
G     The  BTUH  rating  of  the  relief  valve  must  
Water  
Supply  
equal  or  exceed  the  BTUH  input  of  the  
Inlet  
water  heater  as  marked  on  its  rating  plate.
G     No  valve  of  any  type  should  be  installed  
between  the  relief  valve  and  the  water  
heater
G     Discharge  from  the  relief  valve  should  
be  piped  to  a  suitable  drain  to  eliminate  
potential  water  damage.  Piping  used  should  
be  of  a  type  approved  for  the  distribution  of  
hot  water.
G     Hot  and  cold  water  lines  should  be  
insulated  up  to  the  water  heater.  Refer    
to  page  19  for  details.
G     The  discharge  line  must  be  
NO  SMALLER  than  the  outlet  of  the  
relief  valve  and  must  pitch  downward  to  
allow  complete  drainage  (by  gravity)  of  
the  relief  valve  and  discharge  line.
G     The  end  of  the  discharge  line  should  not  
be  threaded  or  concealed  and  should  be  
protected  from  freezing.  No  valve  of  any  
type,  restriction  or  reducer  coupling  should  
be  installed  in  the  discharge  line.
Notice:  Local  codes  govern  the  installation  
of  relief  valves.  If  local  codes  require  that  a  
temperature  and  pressure  relief  valve  should  
be  installed,  the  manufacturer  recommends  
a  type  40XL  Watts  T&P  relief  valve  or  an  
equivalent  model  be  used.
Notice:  Manual  operation  of  relief  valves  
should  be  performed  at  least  once  a  year.  Turn  
off  the  electrical  power  and  gas  shutoff  valve.  
Lift  and  release  lever  on  the  relief  valve  and  
check  the  manual  operation  of  the  relief  valve.  
You  should  take  precaution  to  avoid  contact  
with  the  hot  water  coming  out  of  the  relief  
valve  and  to  prevent  water  damage.
Notice:  If  the  relief  valve  on  the  system  
discharges  periodically,  a  problem  exists  and  
service  to  the  water  system  is  required.
13