Breakdown Of An Eev Closure - Samsung AM009FN1DCH/AA Service Manual

System air conditioner indoor unit
Hide thumbs Also See for AM009FN1DCH/AA:
Table of Contents

Advertisement

4-4-86 Breakdown of an EEV closure

1. How to diagnose
1) During cooling operation (It must satisfy each of the following conditions for over 20minutes.)
Compressor in operation & Indoor unit operation & Thermo On
2) During heating operation (It must satisfy each of the following conditions for over 20minutes.)
· When more than 2 indoor units are on Thermo On heating operating.
· When average high pressure is over 25 kg/cm²G
· 5 minutes after finishing Safety Start.
· Keep indoor units' T(Eva_IN)<T(Room)+3°C and T(Eva_Out)<T(Room)+3°C condition for more than five minutes.
2. How to check
1) Check if the wire of an electronic expansion valve is correctly connected to the PCB of indoor unit.
2) Check if the coil of an electronic expansion valve is correctly plugged into the main body.
3) Check if there is any rust on the surface of the coil of an electronic expansion valve with the naked eye, and then check the resistance between
each terminal to find any wire breaking or short circuit.
4) Press the RESET KEY (K3) of the outdoor unit then see if the same error occurs.
- In case of closure problem, operate the indoor unit in which the error has occurred.
- In case of opening problem, please do not operate the indoor unit in which the error has occurred.
5) If there is no problem with the above checkup items, replace the electronic expansion valve of the troubled indoor unit.
- As an electronic expansion valve replacement is tricky work that requires collecting refrigerant in all systems, please make sure to check the
above items before replacement.
Samsung Electronics
Tair in - Teva in in ≥ 4°C
Tair in - Teva out in ≥ 4°C
Tcond, out - Tair, out > 3°C
Error details
OK
OK
NO
OK
EEV closure breakdown
Troubleshooting
4-111