Fan Motor Overcurrent Error - Samsung AM009FN1DCH/AA Service Manual

System air conditioner indoor unit
Hide thumbs Also See for AM009FN1DCH/AA:
Table of Contents

Advertisement

Troubleshooting

4-4-79 Fan Motor Overcurrent error

Outdoor unit display
· Occurs when overcurrent flows in the IPM.
Judgment Method
· Detected by H/W or S/W
· Installation error
Cause of problem
· Defective Comp
· Defective PCB
1. Cause of problem
Is the outdoor unit installed properly?
Is the resistance value
between different phases of Fan Motor
(U V, V W, W U) less than 10Ω?
Is the resistance between the body of
Fan Motor and chassis MΩ?
Does the Fan Motor connection wire
properly connect to the compressor?
FAN Replace PCB.
4-104
(FAN PCB(FAN1))
(FAN PCB(FAN2))
Power Off
Yes
Yes
Yes
Yes
Yes
· Connector error
· Defective Motor
No
Reinstall after removing obstacle
No
No
Check the connection wire
No
(Check the status of the connection UVW)
Outdoor Fan Motor
Outdoor Fan Motor
Samsung Electronics