This data is entered into Addresses 072, 073 and 074 as shown in diagram above. 3. Connect input as shown in the diagram 4. Apply power to the clock. Page 14 Sapling, Inc. 1633 Republic Road Huntingdon Valley, PA 19006 Phone: (215) 322-6063 Fax: (215) 322-8498 www.Sapling-Inc.com...
Page 15
47 and seconds equals 05 will cause a daily correction. Instructions: 1. Set address 070 to “004” 2. Connect input as shown in the diagram. 3. Apply power to the clock. Page 15 Sapling, Inc. 1633 Republic Road Huntingdon Valley, PA 19006 Phone: (215) 322-6063 Fax: (215) 322-8498 www.Sapling-Inc.com...
Page 16
The clock will jump to the correct time at the end of the correction pulse. Instructions: 1. Set address 070 to “006” 2. Connect input as shown in the diagram. 3. Apply power to the clock. Page 16 Sapling, Inc. 1633 Republic Road Huntingdon Valley, PA 19006 Phone: (215) 322-6063 Fax: (215) 322-8498 www.Sapling-Inc.com...
Page 17
This function can only be used when running a digital clock system (either SBD 1000 or SBD 2000). Instructions: 1. Connect input as shown in the diagram. 2. Apply power to the clock. Page 17 Sapling, Inc. 1633 Republic Road Huntingdon Valley, PA 19006 Phone: (215) 322-6063 Fax: (215) 322-8498 www.Sapling-Inc.com...
What systems can I run off of the SMC 3000 Series Master Clock? The SMC 3000 Series master clock can run 59 minute correction, 58 minute correction, Na- tional Time and Rauland, 2 and 3 wire digital communication (with optional auxiliary power supply installed), and Sapling RS485 systems.
Enter BIT testing and test the relay. For more information on how to enter BIT testing, please refer to the SMC 3000 programming manual. Page 19 Sapling, Inc. 1633 Republic Road Huntingdon Valley, PA 19006 Phone: (215) 322-6063 Fax: (215) 322-8498 www.Sapling-Inc.com...