EXPLANATIONS ON ADJUSTEMENT TABLE FOR HEATING ENGINEERS
Connect header pump for X1/M5
- Program No. 615; Code 0
- Program No. 558.0, ON
42
Code 6 = Tank circulation pump M7 (Room control with software > 1.4)
Pump runs according to timer program of romm control.
Code 7 = Door veil function (Air heater)
Pump M8 when door veil function activated
Code 8 = Primary loop pump M6 (see example 1b). Hydraulic system "2"
(Parameter 552).
Code 9 = RegC1; Basic function of CIR (relay clip in)
Pump M5 as header pump for hydraulic system "67". Only active if
Parameter 558.0 is "ON".
Code 10 = Basic function M5 (K2)
Exit M5 according to hydraulic system for header pump M5.
Code 11 = Function not available for EUROCONDENSE EC
Code 12 = Analogue threshold
M5 activated via limits set by the entry of the relay modules,
CIST or CISP.
If the hydraulic schematic requires a header pump connect its plug to X1/M5.
Programming header pump function:
1. Set program No. 615 to Code 0
2. Set program No. 558.0 to ON
Note: Only one of the following functions can be connected: param. No.
558.0, Code = ON or param. No.615, Code 0 to 12!
Display "558.0 On"