Potterton Eurocondense Plus Installation Manual page 31

Condensing sectional boiler
Table of Contents

Advertisement

CHECKING VALUES
Calling parameter values
Entering the Display mode
Selection and display of individual
values or parameters
Changing parameters:
(only P 0 to P 6)
(+) or (Enter)
(+) bzw. (Enter)
P
(-)
(-)
Operating note
Proceed as follows to obtain the various parameter values (see also Fig. 2
"Control panel"):
The Display mode can be entered by pressing the Display mode button
(10) for a longer period (> 3 sec.) (Display (13): "A..").
Continue to hold down the button to proceed to the various display levels
b, C, d, P and then A again.
Release the button in the desired display level (A, b, C, d, P).
It is possible to switch between the various values/ parameters (0 to max.
7) in the various display levels (A, b, C, d, P) by then momentarily
pressing the Display mode button (10).
Approx. 2 sec. after selecting the parameter, the current value is displayed.
P
It is only possible to change parameters (P0 through P6). For this purpose,
wait until the value for the parameter flashes on the display (13). Basic
procedure:
To increase value (+):
To decrease value (-):
Store value (Enter):
Reject value (Esc)
For confirmation, "P 0" and the newly set value appear alternatingly in the
display (13).
The new value set is taken over by the control centre only
after it is stored!
Complete changes/settings for values within 25 sec. at the latest.
Otherwise, the BMU automatically returns to normal operation.
The display (13) automatically returns to the boiler temperature ("A 1"
after 8 min.
Press Display mode button (10) a number of
times (< 3 sec.)
Press Chimney sweep button (12) a number of
times (< 3 sec.)
Press Display mode button (10) for longer period
> 3 sec.
31