Potterton Eurocondense Plus Installation Manual page 32

Condensing sectional boiler
Table of Contents

Advertisement

ADJUSTEMENT TABLE FOR HEATING ENGINEERS
Table 7 Setting system-dependent parameters in heating specialist level of control centre BMU (with RRG room
control module or RRG service module).
Procedure for changing parameters:
G Press Info button. Then press + / M or + / L buttons until "Initialize BMU parameters"
appears on the display (final user level, only parameters with "X" are displayed!)
G Select heating specialist level: Press both buttons M and L for longer than 3 sec. until the
display "Initialization BMU specialist" appears. (Level for heating specialist).
G Select the desired program No. by pressing the programming keys.
G Set the desired value by pressing the +/- keys.
G After selecting the next program No., the new value is taken over.
G Press the Info button to quit the programming level.
Display on room control module RRG Function
BUM parameter final user level
.
Program
No.
501
TrSmin
502
TrSmax
503
TkSmin
504
TkSmax
505
TkSnorm
506
TvSmin
507
TvSmax
510
TuebBw
511
TkSfrostEin
512
TkSfrostAus
514
TuebVor
516
THG
517
dTbreMinP
519
TiAussenNorm
520
dTrAbsenk
521
dTkTrNenn
523
SdHzEin
524
SdHzAusMin
525
SdHzAusMax
526
SdBwEin1
527
SdBwAus1Min
528
SdBwAus1Max
529
SdBwEin2
531
SdBwAus2Max
532
Sth1
533
Sth2
534
DtR1
535
DtR2
536
NhzMax
537
NqmodNenn
538
NqmodMin
539
NqmodMinBw
541
PhzMax
542
PminHuKw
543
PmaxHuKw
544
ZqNach
545
ZBreMinP
32
Min. room temperature setting
Max. room temperature setting
Min. boiler temperature setting
Max. boiler temperature setting
Boiler temperature setting at standard outdoor temperature 75 °C (not activated)
Min. flow temperature setting, 2
Max. flow temperature setting, 2
Boil temperature setting increase for hot-water charging
Boiler frost protection, switch-on temperature
Boiler frost protection, switch-off temperature
Boiler temperature setting increase for VTC
X
Summer/winter switchover temperature
Max. control difference for termination when
minimum pause time is exceeded
Standard outdoor temperature
X
Reduction of room temperature setting when
timer is connected (HKM + EMS)
Flow/return temperature spread at standard outdoor temperature
Switch-on difference - burner in heating mode
Min. switch-off difference – burner in heating mode
Max. switch-off difference – burner in heating mode
Switch on difference – burner in hot-water
mode on sensor 1
Min. switch-off difference – burner in hot-
water mode on sensor 1
Max. switch-off difference – burner in hot-
water mode on sensor 1
Switch on difference – burner in hot-water
mode on sensor 2
Max. switch-off difference – burner in hot-
water mode on sensor 2
X
Heating curve steepness, heating circuit 1
X
Heating curve steepness, heating circuit 2
X
Correction, room temperature setting, heating circuit 1 0 K
X
Correction, room temperature setting, heating circuit 2 0 K
Max. fan speed at max. output in heating mode
Speed stage at heating system design point
Min. pump speed for heating system
Min. pump speed for layer tank charging
Max. degree of modulation in heating mode
Min. boiler input in kW (Hu)
Max. boiler input in kW (Hu)
Pump overrun delay time, max. 218 min.
Minimum pause time for burner
Basic setting
(set at factory)
10 °C
30 °C
20 °C
88 °C
nd
heating circuit
20 °C
nd
heating circuit
70 °C
18 °C
5 °C
10 °C
10 K
20 °C
30 K
- 20 °C (not activated)
10 K
20 K (not activated)
2)
5 K
2)
4 K
2)
4 K
2)
4 K
2)
2 K
2)
2 K
2)
3 K
2)
3 K
1)
18
1)
15
see tab. 8
30 (not activated)
34 % (not activated)
40 % (not activated)
see tab. 8
see tab. 8
see tab. 8
10 min
120 s
New
setting *)
3)
3)
2)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ec plus 90Ec plus 120Ec plus 160Ec plus 200Ec plus 250

Table of Contents