Summary of Contents for Potterton Eurocondense three
Page 1
September 2011 Eurocondense three Programming Manual – Setting Tables – Programming Floor Standing Condensing Gas Boilers 125 to 300kW Working towards a cleaner future heating specialists...
For whom is this manual intended?....................... Programming............................Programming procedure........................Modification of parameters........................Setting table............................Explanations for setting table....................... 32 Hydraulic and connection plans......................82 Application examples.......................... 82 Legend............................... 115 Gas-fired fuel value boiler EuroCondense three 125-300 kW 358 488 09.10...
Reference to additional information in other documents. 1.3 For whom is this manual intended? This programming and hydraulic system manual is intended for the heating spe- cialist, who installs heating plants. Gas-fired fuel value boiler EuroCondense three 125-300 kW 358 488 09.10...
Boiler Solid fuel boiler Depending on the selection of setting level and Buffer storage tank DHW storage tank programming, not all menu points are visible! Instantaneous water heater Configuration 358 488 09.10 Gas-fired fuel value boiler EuroCondense three 125-300 kW...
Hours / minutes Select with the menu point hours/minutes. Acknowledge selection with Time and date Select with set the hours Hours / minutes (e.g. 15 hours). Acknowledge selection with Gas-fired fuel value boiler EuroCondense three 125-300 kW 358 488 09.10...
Page 7
The previous menu point will be called-up by pressing the ESC-button without ta- king over previously modified values. If no settings are carried out for approxima- tely 8 minutes, the basic display is called-up without taking over previously modi- fied values. 358 488 09.10 Gas-fired fuel value boiler EuroCondense three 125-300 kW...
Operation HC2 Commonly with HC1 Commonly with HC1 | Independently Operation HC3 Commonly with HC1 Commonly with HC1 | Independently Gas-fired fuel value boiler EuroCondense three 125-300 kW 358 488 09.10...
Page 9
Parameter only visible, if heating circuit 2 exists! Pre-selection Mo-Su Mo - Su Mo-Su | Mo-Fr | Sa-Su | Mo |Tu |We | Th | Fr | Sa | Su 1st phase on 06:00 (h/min) 358 488 09.10 Gas-fired fuel value boiler EuroCondense three 125-300 kW...
Page 10
3rd phase on --:-- (h/min) 3rd phase off --:-- (h/min) Default values No | Yes Holidays heating circuit 1 Preselection Period 1 Period 1 ... 8 Start --.-- (day. month) Gas-fired fuel value boiler EuroCondense three 125-300 kW 358 488 09.10...
Page 11
Off | Down to reduced setpoint | Down to frost prot setpoint point Optimum start control max 0 min Optimum stop control max 0 min Reduced setp increase start - - -°C Reduced setp increase end 15°C 358 488 09.10 Gas-fired fuel value boiler EuroCondense three 125-300 kW...
Page 12
Summer/winter heating limit 1030 18°C 24-hour heating limit 1032 -3°C Flow temp setpoint min 1040 8°C Flow temp setpoint max 1041 80°C Flow temp setpoint room stat 1042 65°C Gas-fired fuel value boiler EuroCondense three 125-300 kW 358 488 09.10...
Page 15
1880 - No | Yes Consumer circuit 2 Flow temp setp cons request 1909 70°C DHW charging priority 1924 No | Yes Excess heat draw 1925 Off | On 358 488 09.10 Gas-fired fuel value boiler EuroCondense three 125-300 kW...
Page 16
Boiler pump on heat gen lock 2301 Off | On Impact heat generation lock 2305 Heating mode only Heating mode only | Heating and DHW mode Temp differential max 2316 20°C Gas-fired fuel value boiler EuroCondense three 125-300 kW 358 488 09.10...
Page 18
None | With B4 | With B4 and B42/B41 Auto heat gen lock SD 4721 5°C Temp diff buffer/HC 4722 -3°C Min st tank temp heat mode 4724 - - - °C Gas-fired fuel value boiler EuroCondense three 125-300 kW 358 488 09.10...
Page 19
24h/day | DHW release | Time program 4/DHW El immersion heater control 5062 DHW sensor External thermostat | DHW sensor Automatic push 5070 Off | On Excess heat draw 5085 Off | On 358 488 09.10 Gas-fired fuel value boiler EuroCondense three 125-300 kW...
Page 20
Position on DHW | Position on heating circuit Ctrl boiler pump/DHW valve 5774 All requests All requests | Request HC1/DHW only Solar controlling element 5840 Charging pump Charging pump | Diverting valve Gas-fired fuel value boiler EuroCondense three 125-300 kW 358 488 09.10...
Page 21
Preselected output 10V Contact type H1 5951 NC | NO Voltage value 1 H1 5953 Function value 1 H1 5954 Voltage value 2 H1 5955 Function value 2 H1 5956 358 488 09.10 Gas-fired fuel value boiler EuroCondense three 125-300 kW...
Page 22
Parameters see Relay output QX1 (prog.-no. 5890)! Relay output QX23 module 2 6035 None Parameters see Relay output QX1 (prog.-no. 5890)! Relay output QX21 module 3 6036 None Parameters see Relay output QX1 (prog.-no. 5890)! Gas-fired fuel value boiler EuroCondense three 125-300 kW 358 488 09.10...
Page 23
6063 NC | NO Voltage value 1 H2 module 3 6065 0 Volt Funct value 1 H2 module 3 6066 Voltage value 2 H2 module 3 6067 0 Volt 358 488 09.10 Gas-fired fuel value boiler EuroCondense three 125-300 kW...
Page 24
Local HCs | All HCs in segment | All HCs in system Clock mode 6640 Autonomously Autonomously | Slave without remote setting | Slave with remote set- ting | Master Outside temp source 6650 Fault Fault message 6700 Gas-fired fuel value boiler EuroCondense three 125-300 kW 358 488 09.10...
Page 25
7044 --- months Time since maintenance 7045 0 months Fan speed ionization current 7050 0 rpm Message ionization current 7051 No | Yes Chimney-sweep function 7130 Off | On 358 488 09.10 Gas-fired fuel value boiler EuroCondense three 125-300 kW...
Page 26
7840 Contact state H1 7841 Open | Closed Voltage signal H2 module 1 7845 Contact state H2 module 1 7846 Open | Closed Voltage signal H2 module 2 7848 Gas-fired fuel value boiler EuroCondense three 125-300 kW 358 488 09.10...
Page 27
Parameters see Priority/state source 1 (prog.-no. 8100)! Priority/state source 7 8112 Parameters see Priority/state source 1 (prog.-no. 8100)! Priority/state source 8 8114 Parameters see Priority/state source 1 (prog.-no. 8100)! 358 488 09.10 Gas-fired fuel value boiler EuroCondense three 125-300 kW...
Page 28
Hours run 1st stage 8330 Start counter 1st stage 8331 Hours run heating mode 8338 Hours run DHW 8339 Current phase number 8390 Collector pump 1 8499 Solar ctrl elem buffer 8501 Gas-fired fuel value boiler EuroCondense three 125-300 kW 358 488 09.10...
Page 29
Heat circ mix valve 2 open 8761 Off | On Heat circ mix valve 2 close 8762 Off | On Speed heating circuit pump 2 8765 Room temp 2 8770 Room setpoint 2 8771 358 488 09.10 Gas-fired fuel value boiler EuroCondense three 125-300 kW...
Page 30
Common return temp 8952 Common output setpoint 8962 Buffer temp 1 8980 Buffer setpoint 8981 Buffer temp 2 8982 Buffer temp 3 8983 Relay output QX1 9031 Off | On Gas-fired fuel value boiler EuroCondense three 125-300 kW 358 488 09.10...
Page 31
Fault message Servicing message Setpoint manual control Controller stop setpoint Boiler temp State heating circuit 1 State heating circuit 2 State heating circuit 3 State DHW State boiler State solar 358 488 09.10 Gas-fired fuel value boiler EuroCondense three 125-300 kW...
Press the OK- and the ESC-button simultaneously for at least 3 sec. The lock will be re-activated after leaving the setting level. - Permanent unlocking: At first temporary unlocking, then prog. no. 27 to "Off". Gas-fired fuel value boiler EuroCondense three 125-300 kW 358 488 09.10...
Page 33
Detailed descriptions are in the assembly and setting manual of the room device RGTF. Device lists The state of the respective device will be displayed under programme numbers (130 to 138) 130 to 138. 358 488 09.10 Gas-fired fuel value boiler EuroCondense three 125-300 kW...
Page 34
Preselection 8 vacation periods can be selected with this preselection. (641, 651, 661) Start of holiday Entering the holiday start (642, 652, 662) Gas-fired fuel value boiler EuroCondense three 125-300 kW 358 488 09.10...
Page 35
(e.g. 3.0) which needs to be entered into prog. no. 720, 1020 and 1320 of hte boiler as required. 358 488 09.10 Gas-fired fuel value boiler EuroCondense three 125-300 kW...
Page 36
As soon as the average of the outside temperatures of the last 24 hours drops 1°C below the value set here, the heating circuit switches back into winter mode. Gas-fired fuel value boiler EuroCondense three 125-300 kW 358 488 09.10...
Page 37
For room thermostat mode the flow setpoint set here applies. If the control ist ad- (742, 1042, 1342) justed to - - -°C the flow temperature setpoint results from the outside tempera- ture and the heating curve. 358 488 09.10 Gas-fired fuel value boiler EuroCondense three 125-300 kW...
Page 38
RGB room unit and active room influence. A room sensor must be connected. Fig. 4: Room temp limitation sRE159A Room temperature actual value Room temperature setpoint Room switching difference Pump Time Gas-fired fuel value boiler EuroCondense three 125-300 kW 358 488 09.10...
Page 39
Building time constant (configuration, programme number 6110) Outside temperature composite: 0 hrs 2 hrs 5 hrs 10 hrs 15 hrs 20 hrs 50 hrs 15°C 15,3 10°C 13,4 5°C 21,5 0°C 15,8 -5°C 12,5 358 488 09.10 Gas-fired fuel value boiler EuroCondense three 125-300 kW...
Page 40
= 0, the function is switched off. Fig. 6: Optimum start and stop control Start time set forward Xoff Stop time set forward Time switching program Room temperature setpoint Room temperature actual value Gas-fired fuel value boiler EuroCondense three 125-300 kW 358 488 09.10...
Page 41
(Pumpe ist AUS). In this case, the mixer will be controlled in direction OPEN and CLOSED. The time of activation in direction OPEN corresponds to the drive running time. 358 488 09.10 Gas-fired fuel value boiler EuroCondense three 125-300 kW...
Page 42
(see prog. no. 850). Screed nominal value actual Display of the current floor curing setpoint. (1455) Screed day actual Display of the current day of the floor curing function. (856, 1156, 1456) Gas-fired fuel value boiler EuroCondense three 125-300 kW 358 488 09.10...
Page 43
- No: the temperature request remains unchanged. The calculated correction va- lue was is not added. - Yes: the temperature request includes the flow setpoint correction. 358 488 09.10 Gas-fired fuel value boiler EuroCondense three 125-300 kW...
Page 44
In this case, the time switching programme 4 will be used (see Fig. 10). Gas-fired fuel value boiler EuroCondense three 125-300 kW 358 488 09.10...
Page 45
If no duration has been set, the legionella function has been met immediately on re- aching the legionella function setpoint. 358 488 09.10 Gas-fired fuel value boiler EuroCondense three 125-300 kW...
Page 46
See prog no. 5092. pump (1880, 1930, 1980) Swimming pool Setpoint solar heating When using solar energy, the swimming pool is heated to the setpoint set here. (2055) Gas-fired fuel value boiler EuroCondense three 125-300 kW 358 488 09.10...
Page 47
- After buffer storage tank: the primary controller/feed pump is arranged with existing buffer storage tank hydraulically after the buffer storage tank 358 488 09.10 Gas-fired fuel value boiler EuroCondense three 125-300 kW...
Page 48
The expansion between boiler flow temperature and boiler return temperature is (2317) called the temperature rise. For operation with a modulating pump, the temperature rise is limited with this parameter. Gas-fired fuel value boiler EuroCondense three 125-300 kW 358 488 09.10...
Page 49
With this parameter the maximum output can be limited in full charging mode. charging (2442) Fan output DHW max. With this parameter the maximum fan output for the DHW mode can be restric- (2444) ted. 358 488 09.10 Gas-fired fuel value boiler EuroCondense three 125-300 kW...
Page 50
Switching diff off min DHW max HCs/DHW (2456/2462) (2461) Switching diff off max DHW Switching diff off (2462) min HCs/DHW (2456/2462) Switching diff on HCs/DHW duration Tc (Current temperature) Gas-fired fuel value boiler EuroCondense three 125-300 kW 358 488 09.10...
Page 51
- Last: the last boiler in the addressing always remains as the last boiler; for all other boilers, the boiler sequence is changed after the time set in prog.no. 3540 has elapsed. 358 488 09.10 Gas-fired fuel value boiler EuroCondense three 125-300 kW...
Page 52
Charging temp min buffer / swimming pool Storage temperature Charg temp min DHW st tank Zusätzlich zur Temperaturdifferenz ist das Erreichen einer bestimmten minima- (3812) len Kollektortemperatur für den Speicher-Ladevorgang notwendig. Gas-fired fuel value boiler EuroCondense three 125-300 kW 358 488 09.10...
Page 53
As soon as all setpoints in one level are reached, the ones in the next level are approached, whereby the buffer storage tank again has priority. 358 488 09.10 Gas-fired fuel value boiler EuroCondense three 125-300 kW...
Page 54
In case of overheating danger, charging of the storage will be continued, to remo- (3850) ve heat. When reaching the storage safety temperature, charging of the storage will be interrupted. Gas-fired fuel value boiler EuroCondense three 125-300 kW 358 488 09.10...
Page 55
Setpoint min The boiler pump is only put into operation if the boiler temperature has reached (4110) the minimum setpoint set here in addition to the necessary temperature diffe- rence. 358 488 09.10 Gas-fired fuel value boiler EuroCondense three 125-300 kW...
Page 56
Auto heat gen lock SD The heat source will be locked if the temperature in the buffer storage tank is hig- (4721) her than the boiler setpoint+ auto heat generation lock SD. Gas-fired fuel value boiler EuroCondense three 125-300 kW 358 488 09.10...
Page 57
Note: To activate the return redirection the relay outlet QX1, QX2, QX3 (prog. no. 5890-5892) for the buffer deflector valve and the sensor inlet BX1, BX2, BX3 (prog. no. 5930-5932) for the rail return sensor B73 must also be configured. 358 488 09.10 Gas-fired fuel value boiler EuroCondense three 125-300 kW...
Page 58
Fig. 16: Charge push forward time Heating programme several times/day DHW release C0003410 Gas-fired fuel value boiler EuroCondense three 125-300 kW 358 488 09.10...
Page 59
Off: the function is switched off. Always: the function always affects. Automatic The function only takes effect if the heat generator cannot deliver heat or is not available (malfunction, heat source block). 358 488 09.10 Gas-fired fuel value boiler EuroCondense three 125-300 kW...
Page 60
If an excess temperature discharge is activated, the excess energy can be discharged through a heat draw of the room heating. This can be separate- ly set for each heating circuit. Gas-fired fuel value boiler EuroCondense three 125-300 kW 358 488 09.10...
Page 61
Flow setp compensation Tn The reset time Tn determines the reaction speed of the controller when compen- (5144) sating for remaining controller differences. A shorter reset time Tn leads to faster compensating. 358 488 09.10 Gas-fired fuel value boiler EuroCondense three 125-300 kW...
Page 62
- None: DHW-charge de-activated via Q3. (5731) - Charge pump: DHW-charging via the connection of a charge pump to Q3/Y3. - Deflecting valve: DHW-charging via connection of a deflecting valve at Q3/Y3. Gas-fired fuel value boiler EuroCondense three 125-300 kW 358 488 09.10...
Page 63
DHW. - No: No combined storage exists. - Yes: A combined storage exists. 358 488 09.10 Gas-fired fuel value boiler EuroCondense three 125-300 kW...
Page 64
- Heating circuit pump HC1 /HC2: The relay is used for actuating the heating cir- cuit pump Q2/Q6. - DHW controlling element Q3: Depending on the hydraulics a connected DHW charging pump or diverting valve. Gas-fired fuel value boiler EuroCondense three 125-300 kW 358 488 09.10...
Page 65
- Optg mode changeover HC1 to HC3: Changeover of operating modes of the hea- ting circuits to protective operation or reduced operation. Locking of domestic hot water charging is only possible under the setting Optg mode change HCs+DHW. 358 488 09.10 Gas-fired fuel value boiler EuroCondense three 125-300 kW...
Page 66
The linear sensor curve is defined over two fixed points. The setting is done with Function values 1/2 H4 two parameter pairs for function value and frequency value (F1 / U1 and F2 / U2). (5973-5976) Gas-fired fuel value boiler EuroCondense three 125-300 kW 358 488 09.10...
Page 67
(F1 / U1 and F2 / U2). (6049, 6051, 6057, 6059, 6065, 6067) Function values 1/2 H2 mo- dule 1-3 (6050, 6052, 6058, 6060, 6066, 6068) 358 488 09.10 Gas-fired fuel value boiler EuroCondense three 125-300 kW...
Page 68
Selection of used sensor types for measurement of the collector temperature. (6097) Readjustm coll sensor 1 Setting a correction value for collector sensor 1. (6098) Readjustm outside sensor Setting a correction value for outside sensor. (6100) Gas-fired fuel value boiler EuroCondense three 125-300 kW 358 488 09.10...
Page 69
Tab. 3 (Page 69) (6212, 6213, 6215, 6217) Tab. 3: Check no. heat source 1 (prog.-no. 6212) Solar No solar DHW/B DHW+B DHW/B 358 488 09.10 Gas-fired fuel value boiler EuroCondense three 125-300 kW...
Page 71
(6623) - Centrally: depending on the settings made in prog no. 6620 either the heating circuit in the segment or in the entire system is switched on and off. 358 488 09.10 Gas-fired fuel value boiler EuroCondense three 125-300 kW...
Page 72
Error history/error codes The last 20 error messages with error code and time of error occurrence will be (6800 - 6995) stored in the error storage. Gas-fired fuel value boiler EuroCondense three 125-300 kW 358 488 09.10...
Page 73
(7170) PStick storage pos Via the parameter PStick Storage Pos the data set (data set number on the stick) (7250) can be selected which should be written or read. 358 488 09.10 Gas-fired fuel value boiler EuroCondense three 125-300 kW...
Page 74
- Reading disabled: the parameterization position is in the ABORT condition. Only limited actions are possible to remove the parameterization position. Input/output test Input/output tests Tests for checking the connected components for function. (7700 - 7872) Gas-fired fuel value boiler EuroCondense three 125-300 kW 358 488 09.10...
Page 75
Frost protection active Frost prot room active Frost protection flow active Frost prot plant active Summer operation Summer operation 24-hour Eco active Setback reduced Setback frost protection Room temp limitation 358 488 09.10 Gas-fired fuel value boiler EuroCondense three 125-300 kW...
Page 76
Overrun active Overrun active Standby charging Standby charging Charged Charged, max st tank temp Charged, max charging temp Charged, legionella temp Charged, nominal temp Charged, reduced temp Ready Ready Gas-fired fuel value boiler EuroCondense three 125-300 kW 358 488 09.10...
Page 77
In part load op for HC In part load op for HC Released for HC Released for HC Overrun active Overrun active Released Released Frost protection active Frost prot plant active 358 488 09.10 Gas-fired fuel value boiler EuroCondense three 125-300 kW...
Page 78
Charging buffer+swi pool Charging DHW Charging DHW Charging buffer Charging buffer Charging swimming pool Charging swimming pool Radiation insufficient Min charg temp not reached Temp diff insufficient Radiation insufficient Gas-fired fuel value boiler EuroCondense three 125-300 kW 358 488 09.10...
Page 79
End user (E) Commissioning, Technician (menu state) Fault position Fault position Start prevention Start prevention In operation In operation Commissioning Safety time Prepurge Commissioning Postpurge Shutdown 213 Home mode Standby Standby 358 488 09.10 Gas-fired fuel value boiler EuroCondense three 125-300 kW...
Page 80
Heating mode source off Cold Cold Diagnostics cascade/heat generation/consumers Diagnostics cascade/heat ge- Displays of different nominal and actual values, relay switching statuses and neration/consumers counter statuses for diagnosis purposes. (8100 - 9058) Gas-fired fuel value boiler EuroCondense three 125-300 kW 358 488 09.10...
Page 81
- Prog. no. 9627 equates to the shift of the fan characteristic curve in Y-direction (9627) Info Option Display of different information values which depend on the current operation state. Furthermore, informations about the different states are displayed (see sec- tion State). 358 488 09.10 Gas-fired fuel value boiler EuroCondense three 125-300 kW...
Hydraulic and connection plans 3.2 Legend 358 488 09.10 Gas-fired fuel value boiler EuroCondense three 125-300 kW...
Page 116
Manual adjustment of burner load Manual control Operating unit -Basic setting Optimum start and stop control Quick setback Reduced setpoint increase Room influence Software version State Summer/winter heating limit Gas-fired fuel value boiler EuroCondense three 125-300 kW 358 488 09.10...
Page 117
Space for notes 358 488 09.10 Gas-fired fuel value boiler EuroCondense three 125-300 kW...
Page 118
Space for notes Gas-fired fuel value boiler EuroCondense three 125-300 kW 358 488 09.10...
Page 119
Space for notes 358 488 09.10 Gas-fired fuel value boiler EuroCondense three 125-300 kW...