Page 1
To be kept by the user July 2013 Eurocondense three Installation operation and maintenance manual Floor Standing Condensing Gas Boilers 125 to 300kW Working towards a cleaner future heating specialists...
Table of contents Regarding this Manual......................... Content of this manual......................Overview table......................... Used symbols........................... For whom is this manual intended?.................... Safety..............................Uso appropriato........................General safety instructions......................Regulations and standards......................Liquid gas under ground......................CE-Marking..........................Conformity declaration......................Technical Data............................ 10 Dimensions and connections..................... 10 Technical Data.........................
Page 3
5.12.7 Protection against contact................... 40 Commissioning........................... 41 Menu-Commissioning......................41 Check water pressure........................ 41 Switching-on........................... 41 Temperatures for heating and drinking water................42 Individual time programme....................... 42 Instruction for the customer...................... 42 Operation............................44 Operating elements........................44 Display............................ 45 Setting up heating operation..................... 45 Stop drinking water operation....................
Regarding this Manual 1. Regarding this Manual Read this instruction thoroughly before operating the device! These instructions are from the original German document. 1.1 Content of this manual This manual contains the instructions for the installation of the boilers EuroCon- dense three for standard application with 1 pumped heating circuit and 1 DHW storage tank.
Regarding this Manual 1.3 Used symbols Danger! Danger exists for body and life in case it is not observed. Danger of electric shock! In case it is not observed, danger from electricity exists for body and life! Caution! If warning is not observed, danger exists for environment and the device. Note/tip: Here, you can find background information and useful tips.
Safety 2. Safety Danger! Observe the following safety information! Otherwise you are endangering yourself and others. 2.1 Uso appropriato Le caldaie condensazione a gas della serie EuroCondense three sono generatori di calore in impianti di riscaldamento ad acqua sanitaria secondo DIN EN 12828. Soddisfano le norme DIN EN 676, DIN 4702 parte 6 e DIN EN 677, tipo installazione Per i tipi installazione C osservare le istruzioni del set di accessori.
Safety 2.3 Regulations and standards Beside the general technical rules, the relevant standards, regulations, ordinances and guidelines should be followed: - DIN 4109; Noise protection in construction engineering - DIN EN 12828; Heating plants in buildings - EnEV - Energy saving regulation - Federal Immission Control Ordinance 3.
Technical Data Tab. 1: Dimensions Model Description EC three EC three EC three EC three EC three Dimension A Gas Connection R 1" R 1½" R 1½" R 1½" R 1½" Dimension B Safety Group Connection R 1" R 1" R 1¼"...
Page 12
Technical Data Model EC three EC three EC three EC three EC three Supply pressure for natural gas min. 18 mbar - max. 25 mbar 9.3 (9.1-9.5 allowed) -content natural gas Supply pressure LPG nominal 37 bar -content LPG 11.0 (10.8-11.2 allowed) Max.
Technical Data 3.3 Hydraulic resistance Fig. 2: Hydraulic resistance SGB 125 - 300 E EC three 125 E EC three 170 E EC three 215 E EC three 300 E EC three 260 E 3 /h] Water mass flow 7308536-02 06.13...
Before installation 4. Before installation 4.1 Converting the exhaust and supply air connection The exhaust and supply air connection can be converted to adapt to the local con- ditions of the installation room. 4.1.1 Converting the exhaust connection In the following picture the conversion of the top passage to the side or rear pas- sage of the exhaust connection is represented.
Page 17
Before installation Fig. 5: Conversion of the supply air connection Side supply air connection (A) 1. Remove lower rear wall (2) of the EuroCondense three 2. Loosen screws and remove the cover plate (1) 3. Remove the intake pipe leading upward from the intake pipe elbow (3) 4.
The instructions of the additive manufacturer must be observed. Released additives Currently, the following agents have been approved by Potterton Commercial: - “Full heating protection“ from Fernox - “Sentinel 100“ from GE Betz As a single frost protection agent, also Tyfocor®...
Before installation 4.3.1 Further information on the heating water - The water must not have any foreign matter, such as sweat beads, rust particles, scale or sludge. During filling, flush the system until only clean water runs out. When flushing the system,ensure that the water does not flow through the heat exchanger in the boiler, that the thermostatic radiator valves are removed and the valve inserts are set to the maximum flow rate.
Page 20
Fig. 6: Diagramm Wasserhärte EC three 300 EC three 260 EC three 215 EC three 170 EC three 125 32 34 36 38 °e Water hardness Beschreibung: Der Kesseltyp, die Wasserhärte und das Wasservolumen der Anlage müssen bekannt sein. Liegt das Volumen oberhalb der Kurve, ist eine Teil-Enthärtung des Leitungswassers oder ein Zusatz von Härtestabilisatoren erfor-...
Before installation 4.4 Notes for installation location Caution! Danger of damage from water! The following has to be observed for the installation of the EuroCondense three: In order to prevent damage due to water, particularly due to leakages in the DHW storage tank, suitable precautionary measures should be taken regarding installa- tion.
Before installation 4.5 Space requirement Fig. 7: Recommended space requirement EC three 125 EC three 170 EC three 215 EC three 260 EC three 300 Dimension A (front) 60 cm 70 cm 80 cm 90 cm 100 cm Dimension B (above)
Before installation 4.6 Transportation Fig. 8: Transport equipment For transporting the boiler to the installation location using a crane, transport eyes found on the top of the boiler ( Fig. 8 , Pos. 1) can be used. Remove the centre cov- ering lid of the EuroCondense three to do this.
Installation 5. Installation 5.1 Connect heating circuit Note: It is recommended that a filter be fitted in the heating return. In the case of old plants, the whole heating plant should be thorougly flushed before installa- tion. Safety valve In case of open heating plants, connect the safety header and return pipeline; in case of closed heating plants install the expansion vessel and safety valve.
Installation Modell Flue Size Maximum Flue Length incl. one 87° elbow EC three 125 Ø 160 mm 60 m EC three 170 Ø 160 mm 50 m EC three 215 Ø 200 mm 60 m EC three 260 Ø 200 mm...
(see Fig. 9 ). Moreover, the following parametres of the LMS control have to be adapted - see the values of the following tables: EC three 125 EC three 170 EC three 215 Function Prog.
Installation 5.11 Check and adjust CO2 content Fig. 9: Gas valve 1 Compensation line 4 Gas pressure monitor 2 Adjustment screw for full load (Allen key 3 mm) 5 Adjustment screw for low load (Torx TX 40) 3 Measuring nozzle for inlet pressure Set CO -content at max.
Installation 5.12 Electrical connection (general) Risk of electric shock! Risk to life through incorrect work! All electrical work in connection with the installation must only be carried out by a qualified electrician. - Mains supply AC 230 V +6% -10%, 50 Hz In Germany the VDE 0100 and local regulations must be followed during installa- tion;...
5.12.6 Replacing cables All connecting cables apart from the mains cable must be replaced when necessa- ry with Potterton Commercial special cables. When replacing the mains cable only cables complying with BS6500 must be used. 5.12.7 Protection against contact...
Commissioning 6. Commissioning Danger! The Commissioning must only be carried out by an approved heating spe- cialist! The heating specialist checks the tightnesss of connections, the correct functioning of all regulating, control and safety installations and measures the combustion values. In case of incorrect performance possible danger of considera- ble damage to persons, environment and property! Caution! In dusty environment, e.g.
Commissioning Switch on heating isolator switch 2. Open gas shut-off installation 3. Open front panel cover and switch on the operating switch on the front panel of the boiler xxxxxxxxxxxxxx Select the operation mode automatic operation with the operation mode but- Auto ton on the control unit Set the required room temperature on the rotating knob of the control unit...
Page 43
Commissioning - the air inlet must not be restricted; - flammable materials and liquids must not be stored in the vicinity of the gas boiler; - the customer has to carry out the following control checks himself: - pressure check on the manometer; - check the discharge from the safety valve;...
Operation 7.2 Display Fig. 12: Symbols on the display sRE081B Meaning of the displayed symbols Heating to set comfort tempera- Cooling active (heat pump only) ture Heating to Compressor in operation set reduced tempera- (heat pump only) ture Heating to set frost pro- Service message tection temperature Current process...
Operation Auto Automatic operation - Heating operation according to time programme - Nominal temperature values comfort or reduced according to time pro- gramme - Protection functions (plant frost protection, overheating protection) activated - Automatic summer/winter switch-over (automatic switching over between heating and summer operation from a certain outside temperature) - Automatic day heating limit (automatic change-over between heating and sum- mer operation, if outside temperature exceeds the nominal room value)
Operation Setting reduced setpoint: 1. Press OK button 2. Select heating circuit. 3. Press OK button 4. Select parameter Reduced setpoint 5. Press OK button 6. Set reduced setpoint with the control knob 7. Press OK button 8. Leave programming level by pressing the operation mode button heating oper- ation 7.6 Display information Various temperatures and messages can be called up by pushing the information...
Operation 7.8 Servicing message If the maintenance sign appears in the display, a maintenance message exists or the heating system is in special operation. - Press information button (i) - Further information can be called up (see section Maintenance code- table). Note: The maintenance message has not been activated by the setting in the fac- tory.
Programming 8. Programming 8.1 Programming procedure The selection of the setting levels and menu points for end users and heating spe- cialists is carried out by means of the following diagram: Fig. 13: Selection of setting levels and menu points Basic display Boiler temperature Press...
Programming 8.2 Modification of parameters Settings, which are not directly modified via the front panel, have to be carried out in the setting level. The basic programming processs is depicted in the following by the setting of time and date. Boiler temperature Basic display: Press...
Page 51
Programming Time and date Select with set the minutes Hours / minutes (e.g. 30 minutes). Time and date Hours / minutes Acknowledge selection with Press heating circuit operation mode button to return to the basic display. Boiler temperature The previous menu point will be called-up by pressing the ESC-button without tak- ing over previously modified values.
Programming 8.3 Setting table - Not all parameters displayed in the display are listed in the setting table. - Depending on the plant configuration, not all parameters listed in the setting ta- ble are displayed in the display. - In order to get to the setting levels: Enduser (Eu), Commissioning (C) and Engi- neer (E), press OK button;...
Page 53
Programming Function Prog. Standard value Level Operation HC2 Commonly with HC1 Commonly with HC1 | Independently Operation HK3 Commonly with HC1 Commonly with HC1 | Independently Room temperature unit 1 For all assigned heating Only for Heating circuit 1 | For all assigned heating circuits circuits This parameter is only visible in the room device! Occupancy button unit 1...
Page 54
Programming Function Prog. Standard value Level Default values No | Yes Time prog heating circuit 2 Parameter only visible, if heating circuit 2 exists! Preselection Mo - Su Mo-Su | Mo-Fr | Sa-Su | Mo | Tu | We | Th | Fr | Sa | Su 1st phase on 06:00 (h/min) 1st phase off...
Page 55
Programming Function Prog. Standard value Level 2nd phase on --:-- (h/min) 2nd phase off --:-- (h/min) 3rd phase on --:-- (h/min) 3rd phase off --:-- (h/min) Copy? Default values No | Yes Holidays heating circuit 1 Preselection Period 1 Period 1 ... 8 Start --.-- (day.
Page 56
Programming Function Prog. Standard value Level Flow temp setpoint max 80°C Flow temp setpoint room stat - - -°C Delay heat request Room influence - - - % Room temp limitation 0.5°C Boost heating - - -°C Quick setback Down to reduced set- Off | Down to reduced setpoint | Down to frost prot setpoint point Optimum start control max...
Page 57
Programming Function Prog. Standard value Level Comfort setpoint 1010 20.0°C Reduced setpoint 1012 18.0°C Frost protection setpoint 1014 10.0°C Heating curve slope 1020 1.50 Heating curve displacement 1021 0.0°C Heating curve adaption 1026 Off | On Summer/winter heating limit 1030 20°C 24-hour heating limit 1032...
Page 58
Programming Function Prog. Standard value Level Flow setp readj speed ctrl 1190 No | Yes Operating level changeover 1198 Reduced Frost protection | Reduced | Comfort Optg mode changeover 1200 Protection None | Protection | Reduced | Comfort | Automatic Heating circuit 3 Parameter only visible, if heating circuit 3 exists! Operating mode Heating circuit 3...
Page 59
Programming Function Prog. Standard value Level Excess heat draw 1461 Heating mode Off | Heating mode | Always With buffer storage tank 1470 No | Yes With prim contr/system pump 1472 No | Yes Pump speed reduction 1480 Characteristic Operating level | Characteristic Pump speed min 1482 10 %...
Page 60
Programming Function Prog. Standard value Level Excess heat draw 1875 - Off | On With buffer storage tank 1878 - No | Yes With prim contr/system pump 1880 - No | Yes Consumer circuit 2 Flow temp setp cons request 1909 70°C DHW charging priority...
Page 61
10 % Pump speed max 2323 100 % Output nominal 2330 EC three 125: 125 kW EC three 170: 170 kW EC three 215: 215 kW EC three 260: 260 kW EC three 300: 300 kW Output basic stage 2331...
Page 62
Prog. Standard value Level Max fan output heating full charging 2442 EC three 125: 125 kW EC three 170: 170 kW EC three 215: 215 kW EC three 260: 260 kW EC three 300: 300 kW Fan output DHW max.
Page 63
Programming Function Prog. Standard value Level Temp diff on 3810 8°C Temp diff off 3811 4°C Charg temp min DHW st tank 3812 - - - °C Temp diff on buffer 3813 - - - °C Temp diff off buffer 3814 - - - °C Charging temp min buffer...
Page 64
Programming Function Prog. Standard value Level Charging temp max 4750 80°C Recooling temperature 4755 60°C Recooling DHW/HCs 4756 Off | On Recooling collector 4757 Off | Summer | Always With solar integration 4783 No |Yes Temp diff on return div 4790 8°C Temp diff off return div...
Page 65
Programming Function Prog. Standard value Level With buffer storage tank 5090 No | Yes With prim contr/system pump 5092 No | Yes With solar integration 5093 No | Yes Pump speed min 5101 Pump speed max 5102 100% Speed Xp 5103 35°C Speed Tn...
Page 66
Programming Function Prog. Standard value Level External solar exchanger 5841 Jointly Jointly | DHW storage tank | Buffer storage tank Combi storage tank 5870 No | Yes Relay output QX1 5890 Alarm output K10 None | Circulating pump Q4 | El imm heater DHW K6 | Collector pump Q5 | Cons circuit pump VK1 Q15 | Boiler pump Q1 | Alarm output K10 | Heat circuit pump HC3 Q20 | Cons circuit pump VK2 Q18 | System pump Q14 | Heat gen shutoff valve Y4 | Solid fuel boiler pump Q10 |...
Page 68
Programming Function Prog. Standard value Level Relay output QX22 module 3 6037 None Parameters see Relay output QX1 (prog.-no. 5890)! Relay output QX23 module 3 6038 None Parameters see Relay output QX1 (prog.-no. 5890)! Sensor input BX21 module 1 6040 None Parameters see Sensor input BX1 (prog.-no.
Page 69
Programming Function Prog. Standard value Level Funct value 2 H2 module 3 6068 PWM-output P1 6085 Boiler pump Q1 None | Boiler pump Q1 | DHW pump Q3 | DHW interm circ pump Q33 | Heat circuit pump HC1 Q2 | Heat circuit pump HC2 Q6 Heat circuit pump HC3 Q20 | Collector pump Q5 | Solar pump ext exch K9 | Solar pump buffer K8 | Solar pump swi pool K18 Sensor type collector...
Page 70
Programming Function Prog. Standard value Level Fault Fault message 6700 SW diagnostic code 6705 Burn ctrl phase lockout pos 6706 Reset alarm relay 6710 No |Yes Flow temp 1 alarm 6740 - - - min Flow temp 2 alarm 6741 - - - min Flow temp 3 alarm 6742...
Page 71
Programming Function Prog. Standard value Level Chimney-sweep function 7130 Off | On Manual control 7140 Off | On Controller stop function 7143 Off | On Controller stop setpoint 7145 Telephone customer service 7170 PStick storage pos 7250 PStick Reg data set 7251 PStick command 7252...
Page 72
Programming Function Prog. Standard value Level Voltage signal H2 module 2 7848 Contact state H2 module 2 7849 Open | Closed Voltage signal H2 module 3 7851 Contact state H2 module 3 7852 Open | Closed Contact state H4 7860 Open | Closed Frequency H4 7862...
Page 73
Programming Function Prog. Standard value Level Priority/state source 8 8114 Parameters see Priority/state source 1 (prog.no. 8100)! Priority/state source 9 8116 Parameters see Priority/state source 1 (prog.no. 8100)! Priority/state source 10 8118 Parameters see Priority/state source 1 (prog.no. 8100)! Priority/state source 11 8120 Parameters see Priority/state source 1 (prog.no.
Page 74
Programming Function Prog. Standard value Level Hours run heating mode 8338 Hours run DHW 8339 Current phase number 8390 Collector pump 1 8499 Solar ctrl elem buffer 8501 Solar ctrl elem swi pool 8502 Collector temp 1 8510 Collector temp 1 max 8511 Collector temp 1 min 8512...
Page 75
Programming Function Prog. Standard value Level Heat circ mix valve 2 close 8762 Off | On Speed heating circuit pump 2 8765 Room temp 2 8770 Room setpoint 2 Flow temp 2 8773 Flow temp setpoint 2 Room thermostat 2 8779 No demand | Demand Heating circuit pump 3...
Page 76
Burner control Prepurge time 9500 20 s Nominal output prepurging 9504 EC three 125: 59,3 kW EC three 170: 75,5 kW EC three 215: 77,1 kW EC three 260: 97,7 kW EC three 300: 103,9 kW Nominal output ignition load...
Page 77
Programming Function Prog. Standard value Level Fan output/speed slope 9626 EC three 125: 37,1 EC three 170: 27,6 EC three 215: 26,4 EC three 260: 20,1 EC three 300: 19,9 Fan output/speed Y-section 9627 EC three 125: 501,1 EC three 170: 517,2...
Programming Function Prog. Standard value Level Time Telephone customer service 1) Eu = End user; C = Commissioning; E = Engineer Note: Parameters with the program numbers 1- 54 are individual parameters of the operating unit and the room unit and may, therefore, be set differently on both devices.
Page 79
Programming Operator section save basic The data of the control will be written into the room unit (only available for room settings unit). (30) Caution! The data of the room unit will be overwritten! With this, the individual programming of the control in the room unit can be ensured. Operator section activate ba- The data of the operating unit or room unit will be written into the control.
Programming Readjustment room sensor The temperature display of the value, transmitted by the room sensor, can be cor- (54) rected under programme no. 54. Software version Display of the current software version. (70) 8.4.3 Radio Detailed descriptions are in the assembly and setting manual of the room device RGTF.
Programming Copy The time switching program for one day can be copied and assigned to another or (515, 535, 555, 575, 615) several other days. Note: Day blocks cannot be copied. Default values Setting of the default values given in the setting table (516, 536, 556, 576, 616) 8.4.5 Holiday programs The heating circuits may be set to a selectable operation level with the holiday...
Page 82
Programming Determination of the heating curve slope Enter lowest calculated outside temperature according to climate zone (e.g. -1°C in London) into the diagram (see Fig. 14 ) (e.g. vertical line at -1°C). Enter the maxi- mum flow temperature of the heating circuit, which is reached by calculating with -1°C outside temperature at 20°C room temperature e.g., horizontal line at 82°C).
Page 83
Programming Fig. 15: Summer/winter heating limit Outside temp attenuated (Prog.no. 8703) SWHL SWHL Summer/winter heating limit Temperature Time 24-hour heating limit The 24-hour heating limit shuts off the heating circuit if the current outside tem- (732, 1032, 1332) perature increases up to the difference set here of the current operating level (re- duced or comfort set point).
Page 84
Programming Room influence The flow temperature is calculated using the heating curve as a factor of the out- (750, 1050, 1350) side temperature. This type of control assumes that the heating curve is set cor- rectly, since the control does not take any room temperature into consideration in this setting.
Page 85
Programming Boost heating The boost heating is active if the room set point is switched from protection (770, 1070, 1370) mode or reduced mode to comfort mode. During the boost heating the the room set point is increased to the value set here. This causes the actual room tempera- ture to increase to the new set point within a short period of time.
Page 86
Programming -10°C 10,3 -15°C -20°C Duration of the quick setback for setback by 4°C in h: Building time constant (configuration, programme number 6110) Outside temperature composite: 0 hrs 2 hrs 5 hrs 10 hrs 15 h 20 h 50 hrs 15°C 24,1 10°C...
Page 87
Programming Reduced setp increase start For a relatively small required heating output, the reduced room setpoint can be (800, 1100, 1400) raised for cold outside temperatures. The increase is dependent upon the outside Red setp increase end temperature. The lower the outside temperature is, the higher the reduced set- (801, 1101, 1401) point for the room temperature is raised.
Page 88
Programming Floor curing function The floor curing function serves controlled drying out of screed floors (850, 1150, 1450) - Off: the function is switched off. - Functional heating (Fh): Part 1 of the temperature profile will be run through automatically. - Curing heating (Ch): Part 2 of the temperature profile will be run through auto- matically.
Page 89
Programming Excess heat draw If the excess temperature draw is activated via input H1 to H5 or a maximum (861, 1161, 1461) temperature is exceeded in the system, this excess heat energy can be released by a heat draw of the room heating. - Off: the function is switched off.
Programming Operating level changeover Using an external timer above the entrances Hx it can be selected in which oper- (898, 1198, 1498) ating level the heating circuit is switched into. - Frost Protection: - Reduced: - Comfort: Optg mode changeover In case of external changeover of the operating mode per Hx it can be selected, if (900, 1200, 1500) in automatic mode changeover will be carried out from nominal comfort value to...
Page 91
Programming Fig. 22: Release according to time switching programme 4 (example) Charging priority This function ensures that the boiler capacity is primarily made available for DHW (1630) in case of simultaneous capacity demand by room heatings and DHW. - Absolute priority: Mixer and pumped heating circuits are blocked until the DHW has been heated up.
Programming Legionella function circ pump - On: The circulation pump will be switched on in case of active legionella func- (1647) tion. Caution! There exists a hazard of scalding at the tapping locations in case of acti- vated legionella function. Circulating pump release - Time program 3 The DHW circulating pump is enabled subject to time program (1660)
Programming Charging priority solar Setting of which priority the swimming pool will be solar heated. The priority for (2065) the DHW and charging buffer is set under Prog. no. 3822. - Priority 1: the swimming pool is heated, before the buffer is charged. - Priority 2: the swimming pool is heated, while the buffer is charged.
Page 94
Programming Setpoint manual control The Temperature to which the boiler will be contolled in manual control mode (2214) (also see prog. no. 7140). Burner running time min Here the time span after start up of the burner is set in which the switch off dif- (2241) ference is increased by 50 %.
Page 95
Programming Pump modulation - None: the function is switched off. (2320) - Demand: Actuation of the boiler pump occurs with the speed calculated for the DHW pump during DHW mode or with the highest calculated speed for the max. 3 heating circuit pumps during pure heating mode. The calculated pump speed for heating circuit 2 and 3 is only evaluated if these heating circuits are also dependent on the setting of the diverting valve (Pa- rameter boiler pump/DHW diverting valve control).
Page 96
Programming Fan output DHW max. With this parameter the maximum boiler capacity for the DHW mode can be re- (2444) stricted. Note: These are calculated values. The actual output must be calculated using a gas meter, for example. Fan shutdown heating mode This function is used for switching off the supply voltage for the fan.
Programming Switching diff on HCs To avoid unnecessary switch off during transient effects the switch off difference (2454) adapts dynamically depending on the temperature profile (see Fig. 23 ). Switching diff off min HCs (2455) Fig. 23: Switching differential Switching diff off max HCs (2456) Switching diff on DHW (2460)
Programming Release integral source seq A value generated from temperature and time. The following boiler will be (3530) switched on in case of exceeding the set limit. . Reset integral source seq The following boiler will be switched off in case of exceeding the setpoint (3531) Restart lock The restart lock prevents switching back on of a switched off boiler.
Page 99
Programming Fig. 24: charging control /schematically) Tcol Temp diff on Temp diff off Tcmin ON / OFF Collector pump Tkol Collector temp TLmin Charging temp min buffer / swimming pool Storage temperature Charg temp min DHW st tank In addition to the temperature difference, reaching a certain collector tempera- (3812) ture is necessary for the storage charging process.
Page 100
Programming Charging temp min swi pool Temperatures that the collector must have at the least in order to begin charging (3818) a swimming pool. Charging prio storage tank For several combined exchangers in the system, the loading sequence for the (3822) combined storage tank can be defined by setting the loading priority.
Programming Min run time collector pump The collector pump is periodically switched on for the running time set here. (3831) Collector start function ON The time that the collector start function starts or stops is set here. (3832) Collector start function OFF (3833) Collector start funct grad As soon as there is a temperature increase on the collector sensor, the collector...
Programming Temp diff ON/OFF A sufficiently large temperature difference is necessary between the boiler tem- (4130, 4131) perature and the comparative temperature for start-up of the pump. Comparative temp (44133) Fig. 26: Storage tank charging Temp diff on Temp diff off Boiler temperature Comparative actual temperature ON/OFF...
Page 103
Programming Min st tank temp heat mode If the storage tank temperature of the buffer storage tank drops below this value, (4724) the heating circuit is switched of if no generator is available. Charging temp max The buffer storage tank is charged from solar energy up to the set charging tem- (4750) perature maximum.
Programming Full charging The function full charging makes it possible that the released heat source is first (4810) switched off, despite automatic heat source block if the buffer storage tank is fully charged. During active function the heat source parameterized for the fully charging function is first switched off, if the fully charging setpoint is reached or the boiler must be switched off because of burner control.
Page 105
Programming Type of charging Charging a layer storage (if exists): (5022) - Recharging: The cylinder is only reheated at every DHW demand. - Full charging: The cylinder is fully heated at every DHW demand. - Full charging legio: The cylinder is fully heated if the pasteurisation function is enabled;...
Page 106
Programming Recooling temp Setting the temperature for recooling the DHW-storage. (5055) Recooling collector Recooling of the overheated collector through giving off of the energie to the sur- (5057) rounding of the collector. El imm heater optg mode - Replacement: the DHW is only heated by electrical immersion heater if the boil- (5060) er signals a malfunction or a boiler lock exists.
Page 107
Programming With solar integration This function sets whether the DHW storage tank should be filled. (5093) Pump speed limitations Setting of the minimum and maximum speed of the storage tank charging pump (5101, 5102) in percent. Speed Xp The P-band Xp defines the amplification of the controller A smaller Xp value leads (5103) to a higher actuation of the charging pump with equal control difference.
Programming Min start temp diff Q33 This parameter determines switch on delay of the intermediate circuit pump de- (5148) pending on the boiler temperature. The intermediate circuit pump is switched on as soon as the boiler temperature has reached the boiler setpoint plus the value set here.
Page 109
Programming Separate circuit The DHW separate circuit can only be used in a boiler cascade. (5736) - Off: The DHW separate circuit is switched off. Each available boiler can feed the DHW storage tank. - On: The DHW separate circuit is switched on. The DHW charging is only done from the boiler defined for this.
Page 110
Programming - El imm heater DHW K6: With the connected electrical immersion heater, the DHW can be charged according to the operating side DHW storage operating lines electrical immersion heater. Note: The Operating mode is set under programme number 5060. - Collector pump Q5: Connection of a circulating pump in case of solar collector use.
Page 111
Programming - Status information K36: The output is set, when the burner operates. - Flue gas damper K37: This function activates the flue gas damper control. If the flue gas damper control is activated the burner will only start operating, when the flue gas damper is open.
Page 112
Programming - Excess heat discharge: an active excess heat discharge enables, for example, an external source to force the consumer (heating circuit, DHW storage tank, pump Hx) to take up the excess heat. For each consumer it can be set by the parameter excess temperature discharge whether the forced signal is paid attention to and therefore should take part in the heat discharge or not.
Page 113
Programming Fig. 28: Example for two different sensor curves flow Function extension module Specification of functions that are controlled by the extension modules 1 2 and 3. 1/2/3 Multifunctional: For possible functions that can be assigned to the multifunction- (6020 - 6022) al inputs/outputs, see prog.
Page 114
Programming Fig. 29: Example for heat demand 10 V and cooling demand 10 V Flow setpoint [°C] F2=130 F2=100 Voltage at Hx F1=0 U1=0 0,15 U1=10 Function value 1 Function value 2 Voltage value 1 Voltage value 2 PWM-output P1 With this parameter the function for the modulating pumps is specified.
Page 115
Programming Central setp compensation The central setpoint lead monitors the heat generator setpoint to the required (6117) central flow temperature. With the setting the maximum corrector is restricted, even if a large adaptation is required. Frost protection plant The heating circuit pump will be activated by the outside temperature without (6120) heat request If the outside temperature reaches the lower setpoint of -4°C,the heating circuit pump will be activated.
Page 116
Programming Solar DHW+B DHW/B Tab. 8: Check no. storage tank (prog.-no. 6215) Buffer storage DHW storage tank No buffer No DHW storage tank Buffer storage Electric immersion heater Buffer, solar connection Solar connection Buffer, heat generation shutoff valve Charging pump Buffer, solar connection Charging pump, solar connection Heat gen shutoff valve...
Programming 8.4.18 LPB-system Device address/Segment ad- The two-part LPB address of the controller consists of the 2-digit segment num- dress ber and the 2-digit device number. (6600/6601) Bus power supply function - Off: the power supply of the bus system does not take place through the con- (6604) troller.
Programming DHW assignment This setting is only necessary if the control of the DHW charging is done by a (6625) heating circuit time program (see prog. no. 1620 and 5061) - Local HCs: the DHW charging is done only for the local heating circuit. - All HCs in segment: the DHW charging is done for all heating circuits in the seg- ment.
Programming 8.4.20 Service / special operation Burner hours interval Setting of the interval for maintenance of the burner. (7040) Burn hrs since maintenance Burner hours since the last maintenance. (7041) Note: The burner hours are only counted, when the maintenance message has been activated.
Programming PStick command - No operation: this is the base condition. As long as no operation is active on the (7252) stick, this command is displayed. - Reading from stick: starts reading the data from the stick. This operation is only possible with READ sticks.
Page 121
Programming The following messages are possible under Heating circuit: End user (E) Commissioning, Technician (menu state) Monitor has tripped Monitor has tripped Manual control active Manual control active Floor curing function active Floor curing function active Heating mode restricted Overtemp prot active Restricted, boiler protection Restricted, DHW priority Restricted, buffer...
Page 122
Programming The following messages are possible under DHW: End user (E) Commissioning, Technician (menu state) Monitor has tripped Monitor has tripped Manual control active Manual control active Consumption Consumption Holding mode On Holding mode Active Holding mode On Recooling active Recooling via collector Recooling via heat gen Recooling via HCs...
Page 123
Programming The following messages are possible under boiler: End user (Eu) Commissioning, Engineer (menu state) SLT has tripped SLT has tripped Fault Fault Flue gas temp too high Flue gas temp, shutdown Flue gas temp, powerlimitation Limitter has tripped Limitter has tripped Manual control active Manual control active Chimney sweep funct active...
Page 124
Programming The following messages are possible under Solar: End user (E) Commissioning, Technician (menu state) Manual control active Manual control active Fault Fault Frost prot collector active Frost prot collector active Recooling active Recooling active Max st tank temp reached Max st tank temp reached Evaporation prot active Evaporation prot active...
Page 125
Programming The following messages are possible under solid fuel boiler: End user (Eu) Commissioning, Engineer (menu state) Manual control active Manual control active Fault Fault Overtemp prot active Overtemp prot active Released Locked, manual Locked, automatic Min limitation active Min limitation Min limitation, part load Min limitation active In operation for HC...
Programming The following messages are possible under Buffer: End user (Eu) Commissioning, Engineer (menu state) Warm Warm Frost protection active Frost protection active Charg el imm heater El charg, emergency mode El charg, source protection Electric charging defrost Electric charging, forced Electric charging, substitute Charging restricted Charging locked...
Programming 8.4.24 Burner control Prepurge time Pre-venting time. (9500) Note: This parameter must only be changed by a heating specialist! Nominal output prepurging Nominal output fan speed during preventing. (9504) Nominal output ignition load Nominal output fan speed during ignition. (9512) Nominal output Partial load Nominal output fan speed under boiler in LF.
Maintenance 9. Maintenance 9.1 Inspection and need dependent service Note: It is recommended to carry out maintenance of the EuroCondense three annually. Should during inspection the need for maintenance work be found, these should be carried out according to need. Maintenance work includes among others: - Clean EuroCondense three outside.
Maintenance 9.2 Boiler view Fig. 30: Boiler view Eurocondense three 125-170 Flue gas connection Safety group connection Heating flow Heating return Supply air connection Gas connection Boiler control LMS Ignition transformer (below the control unit) Ionisation electrode Ignition electrodes Sight glass Venturi tube (below the control unit) Silencer...
Maintenance Fig. 31: Boiler view Eurocondense three 215-300 Flue gas connection Safety group connection Heating flow Heating return Supply air connection Gas connection Boiler control LMS Ignition transformer (below the control unit) Ionisation electrode Ignition electrodes Sight glass (below the control unit) Venturi tube Silencer Heat exchanger...
Page 131
Maintenance 4. Disconnect connection lines from fan and gas valve Fig. 32: Loosen screws on the exhaust silencer C0004594 5. Remove screws on the flange of the venturi tube (2) and loosen the venturi tube with seal (in the flange) from the exhaust silencer (1). Fig.
Page 132
Maintenance Fig. 34: Remove burner Eurocondense three Eurocondense three 125 - 170 215 - 300 E 7. Remove nuts and washers and pull out the entire burner (5) with burner seal (6) forwards Installing burner The installation of the burner is done in the opposite sequence Note: Use new seals when installing the burner.
Maintenance 9.4 Check combustion room insulation Attention! Check combustion room insulation after removing the burner! After removing the burner the combustion room insulation must be checked for the correct position ( Fig. 35 ) and increased wear. No plate should have slipped and caused large gaps.
Maintenance 9.6 Check and replacing Ignition electrode Note: To avoid an influence of the ionisation current by the ignition, the ignition electrode must only immerse into the edge of the flame. Change ignition electrodes Danger of electric shock! Before performing service work, power to the boiler must be shut off and it must be secured from accidentally being switched back on! Fig.
Maintenance 9.7 Check and replacing ionisation electrode The ionisation electrode must always be in contact with the flame. During burner operation, the measured ionisation flow must following data display: - At minimum power > 5 µA DC (switching threshold at 0.7 µA DC) - At maximum power >...
Maintenance 9.10 Clean heat exchanger 1. Remove burner (see section Installing and removing burner) Fig. 40: Remove the cover of the exhaust collection pan C0004618 2. Remove screws and remove cover (1) of the exhaust collection pan with seal (2) Fig.
Page 138
Maintenance Fig. 42: Siphon C0004620 5. Remove siphon (4) and clean 6. Clean siphon 7. Reinstall siphon 8. Replace the cover of the exhaust collection pan Note: Use a new seal when installing the cover. 9. Reinstall burner (see section Installing and removing burner) Condensing gas boiler Eurocondense three125-300 kW 7308536-02 06.13...
Maintenance 9.11 Clean fan Dismounting the burner 1. Remove burner (see section Installing and removing burner) Fig. 43: Remove fan 2. Remove nuts with washers and release the fan (3) with seal (2) from burner cover (1) 3. Remove screws and release venturi pipe, incl. gas valve (5) with seal (4) from 4.
Maintenance 9.12 Fault switch-off Safety switch-off in case of flame failure during the operation. After every safety switch-off a new ignition attempt is carried out as per program. If this does not result in flame formation a fault switch-off occurs. In case of fault switch-off, the reset button on the control panel should be pressed.
Maintenance 9.13 Fault code table The following is the fault code table. In case of further displayed fault codes, please inform the heating specialist. Fault Fault description Explanations/causes code No error Outside temp sensor fault Connection or AT-sensor, emergency operation Boiler temperature 1 Sensor fault Check connection, inform heating specialist Boiler temperature solid fuel sensor fault...
Page 142
Maintenance Fault Fault description Explanations/causes code Safety temperature limiter lockout No heat removal, STB/interruption, possibly short in gas valve , internal fuse defective; let device cool down and reset; if this fault occurs several times, inform heating specialist Temperature monitor switching off No heat removal;...
Page 143
Maintenance Fault Fault description Explanations/causes code BX/e'module same sens BX/m'grp same sens E'module same funct Mix group same funct E'mod/m'grp same funct Sensor BX1 no function Sensor BX2 no function Sensor BX3 no function Sensor BX21 no function (EM1, EM2 or EM3) Sensor BX22 no function (EM1, EM2 or EM3) Coll pump Q5 missing Coll sensor B6 missing...
Maintenance 9.14 Maintenance code table Maintanance codes Maintenance description Burner operating hours exceeded Burner starts exceeded Maintenance interval exceeded 9.15 Operating phases of the Control Centre LMS Press the information key to display the operating phases. Phase no. Display Operating state Description of function Standby (no heat demands) Burner on stand-by...
Page 145
Index Factory settings Fault 24-hour heating limit Fault code table Fault message Air inlet Floor curing function Application example Flue lenghts Automatic day heating limit Flue system Automatic operation Frost protection plant Automatic summer/winter switch-over Frost protection setpoint Fuses Boiler view -Eurocondense three 125-170 Gas connection -Eurocondense three 215-300...
Page 146
Optimum start and stop control Original spare parts Outside temperature sensor Protection Protection against contact Purging the gas line Quick setback Reduced setpoint Reduced setpoint increase Regulations Replacing cables Requirements for heating circuit water Resistance values Restoring factory setting Room influence Room temperature -Comfort setpoint -Reduced setpoint...
Page 147
Space for notes 7308536-02 06.13 Condensing gas boiler Eurocondense three125-300 kW...
Need help?
Do you have a question about the EC three 125 and is the answer not in the manual?
Questions and answers