NOTICE The figures below show the minimum installation distances allowed to structures and items in the legend.
Generator installations
A
Exhaust
Direction
B
5 ft (1.5 m)
D
18 in (45.7 cm) min
D
Standby
5 ft
(1.5 m)
A
Standby weatherproof enclosure must be at least 5 ft
A
(1.5 m) from windows, doors, any wall opening, shrubs
or vegetation over 12 inches (30.5 cm) in height.
Exhaust outlet side of weatherproof enclosure must
B
have at least 5 ft (1.5 m) minimum clearance from any
structure, shrubs, trees or any kind of vegetation.
Standby weatherproof enclosure must have a
C
minimum of 5 feet (1.5 m) overhead clearance from
any structure, overhang or trees.
NOTICE DO NOT place weatherproof enclosure under a deck
or other type of covered structure that may confine airflow.
D
A
5 ft (1.5 m) min
Standby
A
Exhaust
Direction
B
18 in (45.7 cm) min
5 ft
(1.5 m)
D
18 in (45.7 cm) min
D
Standby
5 ft (1.5 m)
A
Standby Weatherproof enclosure must have a
D
minimum of 18 inches (45.7 cm) clearance from any
structures with or without a fire rating.
D
A
5 ft (1.5 m) min
Standby
Exhaust
Direction
B
A
5 ft (1.5 m) min
Exhaust
Direction
B
15