LG ARUN Series Service Manual page 92

Outdoor unit multi v plus ii system
Hide thumbs Also See for ARUN Series:
Table of Contents

Advertisement

Troubleshooting Guide
Error
Error Type
No.
25*
Master
Input Voltage high/low
251
Slave
252
I Error Diagnosis and Countermeasure Flow Chart
Is input voltage normal?
Yes
Is inverter PCB assembly normal?
Yes
Recheck power and installation condition
* Measuring input voltage
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Error Point
Input voltage is over limited
value of the product (173V
or less, 289V or more)
Check
R~S/S~T/T~R Phase voltage :460V±10% (3Ø 460V)
No
¡ Check connection condition and wiring if power is
abnormal
No
Replace inverter PCB assembly
* Inverter PCB assembly power wiring
- 92 -
Main Reasons
1. Input voltage abnormal (R~S/S~T/T~R)
2. Outdoor unit inverter PCB assembly dam-
age (input voltage sensing part)
208/230V±10% (3Ø 208/230V)
LGE Internal Use Only

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents