LG ARUN Series Service Manual page 90

Outdoor unit multi v plus ii system
Hide thumbs Also See for ARUN Series:
Table of Contents

Advertisement

Troubleshooting Guide
Error
Error Type
No.
23*
Inverter Compressor DC
Master
Link Low Voltage
231
Slave
232
I Error Diagnosis and Countermeasure Flow Chart
Is input voltage normal?
Yes
Is inverter PCB assembly
power connection normal?
Yes
Is inverter PCB assembly normal?
Yes
Recheck power and installation condition
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Error Point
DC Voltage isn't charged
after starting relay on
Check
R~S/S~T/T~R Phase voltage : 460V±10% (3Ø 460V)
No
¡ Check connection condition and wiring if power is
abnormal
Check connection between inverter PCB assembly and
No
bridge diode(misconnection, disconnection)
¡ wiring again if abnormality found
Check inverter PCB assembly IPM normality
No
¡ Replace inverter PCB assembly
- 90 -
Main Reasons
1. DC Link terminal misconnection/terminal
contact fault
2. Starting relay damage
3. Condenser damage
4. Inverter PCB assembly damage
(DC Link voltage sensing part)
5. Input voltage low
208/230V±10% (3Ø 208/230V)