Troubleshooting Guide
Error
Error Type
No.
42*
Sensor error of low
Master 421
pressure
Slave 422
43*
Sensor error of high
Master 431
pressure
Slave 432
I Error diagnosis and countermeasure flow chart
Is sensor connected
to PCB correctly?
Yes
After replacement of
outdoor unit main PCB
is the system normal?
Yes
END
Low pressure sensor
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Error Point
Abnormal value of
sensor
(Open/Short)
Abnormal value of
sensor
(Open/Short)
No
Connect sensor to PCB correctly
No
Replace corresponding
pressure sensor
High pressure sensor
1. Bad connection of low pressure connector
2. Defect of low pressure connector (Open/Short)
3. Defect of outdoor PCB
1. Bad connection of high pressure connector
2. Defect of high pressure connector (Open/Short)
3. Defect of outdoor PCB
- 104 -
Main Reasons
LGE Internal Use Only