LG ARUN Series Service Manual page 106

Outdoor unit multi v plus ii system
Hide thumbs Also See for ARUN Series:
Table of Contents

Advertisement

Troubleshooting Guide
Error
Error Type
No.
50*
ODU 3phase power omis-
Master
sion error
501
Slave
502
I Error Diagnosis and Countermeasure Flow Chart
Is input voltage normal?
Yes
Is main PCB assembly normal?
Yes
Recheck power and installation condition
* Measuring input voltage
* Main PCB power connection
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Error Point
Omitting one or more of
R,S,T input power
Check
R~S/S~T/T~R Phase voltage : 460V±10% (3Ø 460V)
No
¡ Check connection condition and wiring if power is
abnormal
No
Replace Main PCB assembly
* Noise filter wiring
T
S
R
- 106 -
Main Reasons
1. Input Voltage abnormal (R,S,T)
2. Check power Line connection condition
3. Main PCB damage
208/230V±10% (3Ø 208/230V)
T
R
S
LGE Internal Use Only

Hide quick links: