LG ARUN Series Service Manual page 102

Outdoor unit multi v plus ii system
Hide thumbs Also See for ARUN Series:
Table of Contents

Advertisement

Troubleshooting Guide
Error
Error Type
No.
40*
Inverter compressor CT
Master
sensor error
401
Slave
402
I Error Diagnosis and Countermeasure Flow Chart
Is input voltage normal?
Yes
Is inverter PCB assembly normal?
Yes
Recheck power and installation condition
* Measuring input voltage
* Inverter PCB assembly
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Error Point
Micom input voltage isn't
within 2.5V ±0.3V at initial
state of power supply
Check
R~S/S~T/T~R Phase voltage : 460V±10% (3Ø 460V)
No
¡ Check connection condition and wiring if power is
abnormal
No
Replace inverter PCB assembly
* LGMV Part
- 102 -
Main Reasons
1. Input voltage abnormal (R~S/S~T/T~R)
2. ODU inverter PCB damage
(CT sensing part)
208/230V±10% (3Ø 208/230V)
LGE Internal Use Only

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents