LG ARUN Series Service Manual page 25

Outdoor unit multi v plus ii system
Hide thumbs Also See for ARUN Series:
Table of Contents

Advertisement

2.1.2 Oil return control on heating mode
Outdoor Unit
Component
Inv Compressor
Constant Speed Compressor
FAN
Main EEV
Subcooling EEV
4way valve
Hot gas bypass valve
Indoor Unit
Component
Fan
Thermo on unit EEV
Thermo off unit EEV
Oil return signal
I Oil return operation time : 3 min for running step
I Starting condition:same as cooling mode
I Oil return process ends if compressor protection control starts
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Starting
25Hz
Setting Value
OFF
Normal control
Normal control
Max. pulse
Normal control
OFF
Normal control
Normal control
Starting
Normal control
Normal control
Min. pulse
OFF
- 25 -
Running
ON
Normal control
Max. pulse
Max. pulse
Min. pulse
100 pulse
ON
Normal control
Running
OFF
Normal control
1200 pulse
Normal control
1200 pulse
Min. pulse
ON
LGE Internal Use Only
Function
Ending
25Hz
OFF
ON
Ending
OFF

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents