Troubleshooting

10. Troubleshooting
10.1. Self-diagnosis
Indoor unit's LED indication
(1) For the Four-way cassette
During malfunction protection, digital pipe displays as follow:
No
Displaying contents
1
2
3
4
5
6
7
(2) For the other types indoor unit
No.
Type
Contents
1
Normal
Standing-by
2
Normal
System Off
3
Normal
System startup
4
Normal
Forced cooling
Over current protection of the compressor
5
Protection
occurs 4 times in 1h
Outdoor protection (lack of phase, phase
6
Protection
sequence and temperature protection)
Room temperature sensor checking
7
Error
channel is abnormal
Evaporator sensor checking channel is
8
Error
abnormal
Condenser sensor checking channel is
9
Error
abnormal
10
Error
Communication of EEPROM malfunction
Water level alarm/pump sensor
11
Error
malfunction
(3) LEDs' for the indication of outdoor trouble (3 phase type, 14, 16kW)
Type
Contents
Trouble
Phase sequence
Trouble
Lack of phase(A,B)
Trouble
Lack of phase(C)
Trouble
Protection of Low pressure
Trouble
Overload of current
Trouble
Communication malfunction
Trouble
Open-circuit and short-circuit trouble of T3
Open-circuit and short-circuit trouble of
Trouble
T4(High discharge temperature protection)
Trouble
High temperature protection of condenser
118
Malfunction or protection
Indoor
temperature sensor is abnormal
E2
E3
Evaporator temperature sensor is abnormal
Condenser temperature sensor is abnormal
E4
Temperature sensor error of water pump
E5
Outdoor unit malfunction
E6
EEPROM malfunction
E7
Full-water malfunction
E8
LED Flashing
Operation lamp flashes at 0.5Hz
All lamps are off
Operation lamp on
Operation lamp flashes at 5Hz,
Timer lamp on
Lamps of operation, timer,
defrosting (only fan) flashing
simultaneously at 5Hz.
All lamps flashing at 5Hz
Timer lamp flashing at 5Hz
Operation lamp flashing at 5Hz
Defrosting lamp flashing at 5Hz
Operation lamp and timer lamp
flashing at 5Hz
Alarm lamp flashes at 5Hz
LED1
Flash
Flash
Off
Flash
Off
Flash
Off
Off
Flash
MCAC-UTSM-2008-11
Remark
Nothing wrong with the
unit when LED indicate
these contents.
Whole unit is shut
down. It cannot recover
unless power is cut off
Recover automatically
after errors are
eliminated (For T3
malfunction of 5HP,
can't recover
automatically)
LED2
LED3
Off
Off
Off
Off
Off
Off
Flash
Off
Off
Flash
Off
Flash
Flash
Flash
Flash
Off
Flash
Flash
Outdoor Units