5. Insulation Work
5.1 Insulation material and thickness
5.1.1. Insulation material
Insulation material should adopt the material which is able to endure the pipe's temperature: no less than
℃
70
in the high
-pressure side, no less than 120
requirements at the low-pressure side.)
u Example: Heat pump type----Heat-resistant Polyethylene foam (withstand above 120 )
Cooling only type----Polyethylene foam (withstand above 100 )
5.1.2. Thickness choice for insulation material
Insulation material thickness is as follows:
Refrigerant pipe
Drainage pipe
5.2 Refrigerant pipe insulation
5.2.1. Work Procedure
①
Before laying the pipes, the non
②
When the gas proof test is eligible, the jointing area,
insulated
5.2.2. Insulation for non-jointing parts and non-connection parts
wrong
Gas pipe and liquid pipe should
not be put together to insulate
Installation
℃
in the low
Pipe diameter (mm)
Φ6.4—Φ25.4
Φ28.6—Φ38.1
Inner diameterΦ20—Φ32
-jointing parts and non-connection parts should be heat insulated.
Insulate the gas pipe
(cooling only)
-pressure side(For the cooling type machine, no
℃
Adiabatic material thickness
expanding area and the flange area should be heat
right
Insulation Work
℃
10mm
15mm
6mm
Insulate the gas pipe and
liquid pipe