8.12 Electric wiring

Note:
l The air conditioner must use special circuit (over 40A), and wiring by the qualified
electrician according to the wiring rules specified in national standard.
l The grounding wire and the neutral wire shall be strictly separated. Connect the neutral
wire with grounding wire is incorrect.
l The electric leakage breaker must be installed.
l All the electric wire must be copper wire. When wiring, there shall keep a proper distance
between the power line and communication wire to avoid twist together. Otherwise,
signal disturbance will occur, and the air conditioner can not operate normally.
l Power supply: 1PH, 220V~, 50Hz, the power supply connects from the outdoor side.
l The wiring method of power line is Y connection. If the power line is damaged, in order
to avoid risk of electric shock, it must be replaced by the manufacturer or its repair center
or other similar qualified person.
l Specification of wire and short circuit protector in site wiring:
Type
Power
Contents
line
Specificatio
YZW
n
Parameter
6mm2
Note: The signal wire using shielded wire is recommended.
Connection
wire
YZW
3 x
3 x
(1~1.25mm2)
Connection signal wire
YZW
2 x (0.75~1.25mm2)
Short
circuit
protector
----
40A