After dehumification sign, emission sign, 8 sign, OFF sign, up arrow, down arrow display for 3 minutes, the
controller will only display up arrow and down arrow
power on
partial
signs
power on
display
new code selection: press "select" button once, there is up arrow in the LCD, which shows the
press
Selection of
new code will be selected. We always use new code.
"select"
emission
Old code selection: pree "select" button again, there is down arrow in the LCD, which shows the
button
code
old code will be selected.
Press "read" button once, emission sign and deumification sign will keep for 1 second, read the
read unit
indoor unit number, and observe that the flash time of power lamp of indoor unit should
code
correspond with the data in the LCD.
Press "No. 1" button, 1 will flash, then press "SET" button at indoor unit. When a sound "du" of
set No. 1
indoor unit is heard, unit 1 is set, then press "READ" to confirm if the unit number is right.
unit
Press "No. 2" button, 2 will flash, then press "SET" button at indoor unit. When a sound "du" of
set No. 2
indoor unit is heard, unit 2 is set, then press "READ" to confirm if the unit number is right.
unit
Press "No. 3" button, 3 will flash, then press "SET" button at indoor unit. When a sound "du" of
set No. 3
indoor unit is heard, unit 3 is set, then press "READ" to confirm if the unit number is right.
unit
Press "No. 4" button, 4 will flash, then press "SET" button at indoor unit. When a sound "du" of
set No. 4
indoor unit is heard, unit 4 is set, then press "READ" to confirm if the unit number is right.
unit
Press "No. 5" button, 5 will flash, then press "SET" button at indoor unit. When a sound "du" of
set No. 5
indoor unit is heard, unit 5 is set, then press "READ" to confirm if the unit number is right.
unit
Press "No. 6" button, 6 will flash, then press "SET" button at indoor unit. When a sound "du" of
set No. 6
indoor unit is heard, unit 6 is set, then press "READ" to confirm if the unit number is right.
unit
Press button 6 and at the same time in 2 seconds press button 1, then loosen them
set No. 7
simultaneously. The LCD will display "7", which stands for selecting unit 7. And then press button
unit
"set", you can set unit 7.Then press "READ" to confirm if the unit number is right.
Press button 6 and at the same time in 2 seconds press button 2, then loosen them
set No. 8
simultaneously. The LCD will display "8", which stands for selecting unit 8. And then press button
unit
"set", you can set unit 7.Then press "READ" to confirm if the unit number is right.
Confirm the whole air conditioner work normally, then lock all indoor unit number by "LOCK". The
lock unit
locked unit numbers will not change if without the address setting controller.
number
Note: When setting unit number, if indoor unit sounds "du du", which shows this number has exixted in the
system, you should set another unit number.
new code selection: press "select" button once, there is up arrow in the LCD, which shows the
press
new code will be selected. We always use new code.
"select"
Old code selection: pree "select" button again, there is down arrow in the LCD, which shows the
button
old code will be selected.
Press "read" button once, emission sign and deumification sign will keep for 1 second, read the
read unit
indoor unit number, and observe that the flash time of power lamp of indoor unit should
code
correspond with the data in the LCD.
Press "No. 1" button, 1 will flash, then press "SET" button at indoor unit. When a sound "du" of
set No. 1
indoor unit is heard, unit 1 is set, then press "READ" to confirm if the unit number is right.
unit
Press "No. 2" button, 2 will flash, then press "SET" button at indoor unit. When a sound "du" of
set No. 2
indoor unit is heard, unit 2 is set, then press "READ" to confirm if the unit number is right.
unit
Press "No. 3" button, 3 will flash, then press "SET" button at indoor unit. When a sound "du" of
set No. 3
indoor unit is heard, unit 3 is set, then press "READ" to confirm if the unit number is right.
unit
Press "No. 4" button, 4 will flash, then press "SET" button at indoor unit. When a sound "du" of
set No. 4
indoor unit is heard, unit 4 is set, then press "READ" to confirm if the unit number is right.
unit
Press "No. 5" button, 5 will flash, then press "SET" button at indoor unit. When a sound "du" of
set No. 5
indoor unit is heard, unit 5 is set, then press "READ" to confirm if the unit number is right.
unit
Function table for address setting controller
dehumification sign, emission sign, 8 sign, OFF sign, up arrow, down arrow