Majestic 33BDVT Installation Instructions & Homeowner's Manual page 28

Builder top vent direct vent models
Table of Contents

Advertisement

Vermont Castings, Majestic Products.
T
START
•TURN GAS SUPPLY OFF
• TURN ON/OFF SWITCH
TO "ON"
POWER TO MODULE
(24V NORMAL)
YES
SPARK ACROSS
IGNITOR SENSOR GAP
YES
• TURN GAS ON
PILOT BURNER LIGHTS?
YES
SPARK STOPS WHEN
PILOT IS LIT?
YES
MAIN BURNER LIGHTS?
YES
SYSTEM RUNS UNTIL
ON/OFF SWITCH IS IN
"OFF" POSITION
YES
TROUBLESHOOTING
ENDS
33/36/39/43 BDVT
S
ROUBLE
HOOTING
SIT 822 Valve with a Honeywell Electronic Ignitor
Remove glass before servicing.
CHECK: • LINE VOLTAGE (120VAC)
NO
UNPLUG IGNITION LEAD
AND CHECK SPARK
NO
• CHECK IGNITION CABLE GROUND WIRING, CERAMIC INSULATOR
AND GAP. CORRECT AS NECESSARY
• CHECK BOOT OF IGNITION CABLE FOR SIGNS OF MELTING OR
BUCKLING. TAKE PROTECTIVE ACTION TO SHIELD
CABLE AND BOOT FROM EXCESSIVE TEMPERATURES.
NO
• CHECK THAT ALL MANUAL GAS VALVES ARE OPEN, SUPPLY TUBING
AND PRESSURES ARE GOOD, AND PILOT BURNER ORIFICE
IS NOT BLOCKED.
• CHECK ELECTRICAL CONNECTIONS BETWEEN MODULE AND
PILOT OPERATOR ON GAS CONTROL.
• CHECK FOR 24VAC ACROSS PV-MVPV TERMINALS ON MODULE IF
VOLTAGE IS OKAY, REPLACE GAS CONTROL IF NOT, REPLACE
MODULE.
NO
NOTE: IF S8600B GOES INTO LOCKOUT, RESET SYSTEM.
• CHECK CONTINUITY OF IGNITION CABLE AND GROUND WIRE.
• CLEAN FLAME ROD
• CHECK ELECTRICAL CONNECTIONS BETWEEN FLAME ROD & MODULE.
• CHECK FOR CRACKED CERAMIC FLAME ROD INSULATOR.
• CHECK THAT PILOT FLAME COVERS FLAME ROD AND IS STEADY BLUE
• ADJUST PILOT FLAME.
• IF PROBLEM PERSISTS, REPLACE MODULE.
NO
• CHECK FOR 24VAC ACROSS MV-MVPV TERMINALS IF NO
VOLTAGE, REPLACE MODULE.
• CHECK ELECTRICAL CONNECTIONS BETWEEN MODULE AND GAS
CONTROL. IF OKAY, REPLACE GAS CONTROL, OR GAS CONTROL
OPERATOR.
NO
NOTE: IF S8600B GOES INTO LOCKOUT, RESET SYSTEM
• CHECK FOR CONTINUITY OF IGNITION CABLE AND GROUND WIRE.
NOTE: IF GROUND IS POOR OR ERRATIC, SHUTDOWN MAY OCCUR
OCCASIONALLY EVEN THOUGH OPERATION IS NORMAL AT THE TIME
OF CHECKOUT.
• CHECK THAT THE PILOT FLAME COVERS FLAME ROD AND IS STEADY
AND BLUE.
• IF CHECKS ARE OKAY, REPLACE MODULE.
T
G
C
HE
AS
ONTROL
• LOW VOLTAGE TRANSFORMER
(19.5 minimum VAC)
• ON/OFF SWITCH
• WIRING CONNECTIONS
NO
AT MODULE
(24VAC normal)
SPARK OK?
YES
-28-
S
YSTEM
• REPLACE MODULE
10002555/0

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

36bdvt39bdvt43bdvt

Table of Contents