Daikin SiBE81-909 Service Manual page 61

Humidifying air purifier
Table of Contents

Advertisement

Troubleshooting
7.4.4 DC fan locks.
Caution
1
Models Covered
MCK75JVM-K
2
Method of Mal-
function Detection
Abnormality of the fan motor is
detected by revolutions with the Hall
IC while the fan motor is running.
3
Malfunction Deci-
sion conditions
When the fan motor is not revved
up.
4
Supposed Causes
The fan motor is defective.
The power supply PCB or opera-
tion PCB is defective.
Foreign objects in the fan.
The connector is disconnected.
60
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
5
Troubleshooting
Diagnosis
All 4 airflow rate indicators
blink simultaneously.
Disconnect the power
supply plug once and wait
for 3 seconds. And then,
reconnect the power
supply plug.
Retry to operate with the
ON/OFF switch.
Airflow rate indicators
blink then go OFF.
Yes
Is there any foreign
object in the fan?
No
Yes
Is the fan motor connector
disconnected?
No
SiBE81-909
Remedy
NOTE: Turn off the
power before
unplugging the con-
nector. If the con-
nector is unplugged
with the unit turned
on, the fan motor
may be damaged.
(Turn off the power
before plugging in
connector as well.)
Remove the for-
eign objects and
restart operation.
Connect.
[S102]
Replace the fan
motor.
When the indica-
tors blink after
restarting,
replace the power
supply PCB or
the operation
PCB.
Check1
Go to
on
P. 64.
Humidifying Air Purifier

Advertisement