RECOMMENDATIONS FOR PROPER PROTECTION
The following recommendations for the location of fire and burglary detection
devices help provide proper coverage for the protected premises.
Recommendations For Smoke And Heat Detectors
With regard to the number and placement of smoke/heat detectors, we subscribe to the
recommendations contained in the National Fire Protection Association's (NFPA) Standard #72 noted
below.
Early warning fire detection is best achieved by the installation of fire detection equipment in all
rooms and areas of the household as follows: For minimum protection a smoke detector should
be installed outside of each separate sleeping area, and on each additional floor of a multi-floor
family living unit, including basements. The installation of smoke detectors in kitchens, attics
(finished or unfinished), or in garages is not normally recommended.
For maximum protection the NFPA recommends that you install heat or smoke detectors in the
living room, dining room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storage
rooms, basements and attached garages.
In addition, we recommend the following:
• Install a smoke detector inside every bedroom where a smoker sleeps.
• Install a smoke detector inside every bedroom where someone sleeps with the door partly or
completely closed. Smoke could be blocked by the closed door. Also, an alarm in the hallway
outside may not wake up the sleeper if the door is closed.
• Install a smoke detector inside bedrooms where electrical appliances (such as portable
heaters, air conditioners or humidifiers) are used.
• Install a smoke detector at both ends of a hallway if the hallway is more than 40 feet (12
meters) long.
• Install smoke detectors in any room where an alarm control is located, or in any room where
alarm control connections to an AC source or phone lines are made. If detectors are not so
located, a fire within the room could prevent the control from reporting a fire or an intrusion.
DINING
LIVING ROOM
THIS CONTROL COMPLIES WITH NFPA REQUIREMENTS FOR TEMPORAL
PULSE SOUNDING FOR FIRE NOTIFICATION APPLIANCES.
Recommendations For Proper Intrusion Protection
For proper intrusion coverage, sensors should be located at every possible point of entry to a home or
commercial premises. This would include any skylights that may be present, and the upper windows in
a multi-level building.
In addition, we recommend that radio backup be used in a security system so that alarm signals can
still be sent to the alarm monitoring station in the event that the telephone lines are out of order (alarm
signals are normally sent over the phone lines, if connected to an alarm monitoring station).
KITCHEN
BEDROOM
BEDROOM
BEDROOM
BEDROOM
TO
BEDROOM
BEDROOM
BR
KTCHN
.
CLOSED
LVNG RM
DOOR
BASEMENT
– 2 –
KITCHEN
DINING
BDRM
TV ROOM
BDRM
LIVING ROOM
BEDROOM
Smoke Detectors for Minimum Protection
Smoke Detectors for Additional Protection
Heat-Activated Detectors
GARAGE
Need help?
Do you have a question about the FA142C and is the answer not in the manual?
Questions and answers
Why there is no siren output all of sudden
The First Alert FA142C may have no siren output due to the following possible causes:
1. Power Issues – The alarm sounder requires a 12V, 2.0 Amp output. If the power supply is interrupted or the backup battery is depleted, the siren may not function.
2. Blown Fuse – The system has a 3A battery fuse (No. 90–12). If this fuse is blown, it could prevent the siren from operating.
3. Wiring Issues – Incorrect or loose wiring connections to the siren or control panel may cause a lack of output.
4. System Programming – If alarm outputs are not correctly programmed or disabled in the system settings, the siren may not activate.
5. Overloaded Power Output – The auxiliary power output and alarm sounder should not exceed 600mA total for UL installations. If overloaded, the system may shut down the siren output.
Checking these factors can help identify and resolve the issue.
This answer is automatically generated