Mitsubishi Electric SEZ-KD25VAQ Technical & Service Manual page 32

Mr.slim series ceiling concealed
Hide thumbs Also See for SEZ-KD25VAQ:
Table of Contents

Advertisement

6-5. TEST POINT DIAGRAM
6-5-1. Indoor controller board
Fuse(6.3A 250V)
CN01
C955
CN3C
CN32
CN22
CN51
CN41
SW2
SW1
CN01 Power supply voltage (220 - 240VAC)
SWE
Emergency operation
SW1
Model selection
SW2
Capacity setting
CNP
CN32 Remote start/stop adapter
CN22 For MA remote controller cable con-
nection
(10 - 13 VDC (Between 1 and 3.))
CN51 Centralized control
CN41 JAMA standard HA terminal A
CNMF
CN44 Thermistor
(liquid/condenser/evaporator
temperature)
C626
CN4F Float thermistor
PC672
CN20 Thermistor (Inlet temperature)
CN3C Indoor-outdoor transmission
(0 - 24VDC)
CNMF Fan motor output
1 - 4: 310 - 340 VDC
LED1
5 - 4: 15 VDC
6 - 4: 0 - 6.5 VDC
7 - 4: Stop 0 or 15 VDC
LED2
CN20
CNP
Drain-up mechanism output (200VAC)
CN44
CN2L LOSSNAY
CN4F
CN90 Wireless remote controller
SWE
(*1)
V
Voltage on the (-) side of PC672 and
CN2L
FG
C955
(Same with the voltage between 7 (+)
and 4 (-) of CNMF)
V
Voltage between the C955 pins 15
CC
VDC
(Same with the voltage between 5 (+)
LED3
and 4 (-) of CNMF)
V
Voltage between the C626 pins
sp
0VDC (with the fan stopped)
CN90
1 - 6.5VDC (with the fan in operation)
(Same with the voltage between 6 (+)
and 4 (-) of CNMF)
30
Run 7.5 VDC
(0 - 15 pulse)