Samsung RD040MHXCA Series Installation Manual page 27

Samsung air conditioner installation manual
Table of Contents

Advertisement

Specification of Electronic Wire of the Outdoor Unit
Power
Outdoor unit
Supply
RD040MHXCA
208V-230V~/60Hz
Series
RD050MHXCA
208V-230V~/60Hz
Series
The power cable is not supplied with the air conditioner.
MCCB : Molded Case Circuit Breaker, ELB : Earth Leakage Breaker.
ELCB:Earth Leakage Circuit Breaker.
Specification of Electronic Wire of the Indoor Unit
Power Supply
Max/Min(V)
208-230V~/60Hz
187/253
Select the thickness and length of power cable for total drop of electric pressure to be less than
10%(On 208V-230V~ lnput voltage basis).
CAUTION
 You should connect the power cable into the power cable terminal and
fasten it with a clamp.
 To protect the product from water and possible shock, you should keep
the power cable and the connection cord of the indoor and outdoor
units in the iron pipe.
 Must keep the cable in a protection tube.
 Keep distances of 50mm(2inch) or more between power cable and
communication cable.
 Each indoor unit should be supplied between maximum and minimum
voltage values(253V~187V).
FJM RD040MHXCA_IM_32073_E_3.17.10.indd 27
Max.
MCCB+ELB(A)
Max/Min(V)
Current
or ELCB(A)
187/253
28.0
187/253
30.0
Power Supply (1 Phase)
Power cable
(mm
(inch
))
2
2
Decided by power drop
2.5(0.0038)
among indoor units
Power cable
(mm
(inch
))
2
2
CV
VV
40
4(0.006) 6(0.009)
40
4(0.006) 6(0.009)
Earth Cable
(mm
(inch
))
2
2
Max length
2.5(0.0038)
I
U
NSTALLING THE
NIT
Earth cable
Max Length
(mm
(inch
))
(m (ft))
2
2
6(0.009)
18(59)
6(0.009)
18(59)
Communication
cable (mm
(inch
))
2
2
0.75~1.25
(0.0012~0.0019)
27
E-